DIN VDE 0271/0276 power cables (Germany)

Germany · 51 symbols · How to read a DIN VDE 0271/0276 power cables (Germany) cable code

NVDE Standard
(N)Similar To VDE Standard
AAluminium Conductor
sSector Shaped Conductor
oOval Conductor
hHollow Circular Conductor
/vCompact Conductor
YPolyvinyl Chloride (PVC)
2YPolyethylene (PE)
2XCross-Linked Polyethylene (XLPE)
CConcentric Copper Conductor
CWConcentric Copper Conductor, Wave Form (Ceander)
SECopper Screen, Over Individual Core
RRound Steel Wire
R(AL)Round Aluminium Wire Armour
FFlat Galvanized Steel Wire
GHelical Galvanized Steel Tape
BSteel Tape Armour
(F)Longitudinal Water Resistant Tape
(FL)Longitudinally And Radially Watertight (Swelling Tape Plus Bonded Al Laminate)
(L)Radial Water Resistant Tape
-OWithout Earthing Core (No Green/Yellow Core)
-JWith Earthing Core (Green/Yellow Core)
KLead Sheath
CEConcentric Copper Conductor On Each Core
-ZNumbered Cores
-BCore Colours acc. VDE 0293 (HD308)
HXHalogen-Free Materials
E30Circuit Integrity 30 Minutes (DIN 4102-12)
E60Circuit Integrity 60 Minutes (DIN 4102-12)
FLLongitudinal & Radial Water Resistant Tape
RERound Solid Conductor, IEC 60228 Class 1 (size field)
RMRound Stranded Conductor, IEC 60228 Class 2 (size field)
SESector-Shaped Solid Conductor, IEC 60228 Class 1 (size field)
SMSector-Shaped Stranded Conductor, IEC 60228 Class 2 (size field)
RFRound Fine-Wire (Flexible) Conductor, IEC 60228 Class 5 (size field)
RMSRound Segmental (Milliken) Stranded Conductor, IEC 60228 Class 2 (size field)
RMVRound Stranded Compacted Conductor, IEC 60228 Class 2 (size field)
SMVSector-Shaped Stranded Compacted Conductor, IEC 60228 Class 2 (size field)
KLAluminium Sheath, Pressed Or Welded, Smooth
KLDAluminium Sheath, Corrugated (XLPE HV Cables); Paper Cables: Smooth Pressed Aluminium Sheath With Expansion Elements
R(A)Round Aluminium Wire Armour (Written Form Of R(AL))
E90Circuit Integrity 90 Minutes (DIN 4102-12)
AADouble Outer Covering Of Fibrous Material Or Glass-Fibre Tape
SCopper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores
GbCounter Helix Of Steel Tape Over Wire Armour (Older Use: Mining Cable)
-JZWith Green/Yellow Earth Core, Other Cores Numbered (White Numbers On Black)
-OZWithout Green/Yellow Earth Core, All Cores Numbered (White Numbers On Black)
FEInsulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180 = 180 Min
HHalogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)
EAfter N: Cores Individually Metal-Sheathed (Multi-Sheath Paper Cable, E.g. NEKEBA); After The Metal Sheath: Protective Covering With Embedded Elastomer Or Plastic Tape

Cable designations read in this system