NAY2Y
NAY2Y is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; Y = Polyvinyl Chloride (PVC); 2Y = Polyethylene (PE).
3 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of NAY2Y 3x16 0.6/1 kV:
NAY2Y: N = VDE Standard; A = Aluminium Conductor; Y = Polyvinyl Chloride (PVC); 2Y = Polyethylene (PE)3x16 0.6/1 kV: 3 cores, each aluminium 16 mm²; rated voltage 0.6/1 kV
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
A | Aluminium Conductor |
Y | Polyvinyl Chloride (PVC) |
2Y | Polyethylene (PE) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
TS 621 / TSE (Turkey)
| Symbol | Meaning |
|---|---|
N | Cable Resistant To Light & Normal Mechanical Load For Fixed Installation |
A | Aluminium Conductor |
Y2 | Round Aluminium Wire Armour |
Y | Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212) |
DIN VDE 0250 cords, control and special cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
A | Single-Core Non-Sheathed Cable |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
2Y | Polyethylene (PE) |
How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.
What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).
What does 2Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2Y means Polyethylene (PE).
Fire behaviour (EU CPR)
PE sheath (2Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NAY2Y: equivalents in other countries
Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | Al/PVC/PE 3x16 0,6/1 kV (to IEC 60502-1) | Equivalent | every value the same |
| India | IS 1554 (Part 1) | AYY 3x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); Inner covering / bedding 1 → 0.3 mm; Sheath material PE → PVC; Overall diameter 20.47 → 19.07 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
NAY2Y as the cable designer builds it, 3x16 0.6/1 kV
Overall diameter 20.5 mm, about 420 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Filler | PP | 14.9 | |
| Inner covering / bedding | PVC | 1.0 | 16.9 |
| Sheath | PE | 1.8 | 20.5 |
NAY2Y on a drum
The smallest drum that passes every check, for 20.5 mm and about 420 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 10 | 281–288 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 13 of 13 | 564–585 kg |
Barrel at least 15 × OD = 307 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NAY2Y
NAY2Y belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with NAY2Y
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.