AYY

AYY is a DIN VDE 0271/0276 power cables (Germany) cable designation: A = Aluminium Conductor; Y = Polyvinyl Chloride (PVC); Y = Polyvinyl Chloride (PVC).

6 coding systems recognise this code

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
AAluminium Conductor
YPolyvinyl Chloride (PVC)
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)

SymbolMeaning
AOutdoor Cable
YPolyvinyl Chloride (PVC)
YPolyvinyl Chloride (PVC)

How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
ATwin Cable
YPolyethylene (PE) Or Polyolefin
YPolyethylene (PE) Or Polyolefin

How to read a China (GB / JB/T / MT cable model codes) cable code

Romania (STAS 9436 national symbols)

SymbolMeaning
AAluminium Conductor
YPolyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering
YPolyvinyl Chloride (PVC) Insulation, Sheath Or Outer Covering

How to read a Romania (STAS 9436 national symbols) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
AAluminium Conductor
YTextile Or Metallic Carrying Component Between Cores
YTextile Or Metallic Carrying Component Between Cores

How to read a CEI-UNEL 35011 (Italy) cable code

India (IS 1554 / IS 7098 cable code)

SymbolMeaning
AAluminium Conductor
YPolyvinyl Chloride (PVC)
YPolyvinyl Chloride (PVC)

How to read a India (IS 1554 / IS 7098 cable code) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.

What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

AYY: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NAYY 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules
IndiaIS 1554 (Part 1)AYY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

AYY as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 120 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
SheathPVC1.49.7

AYY on a drum

The smallest drum that passes every check, for 9.7 mm and about 120 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1467 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16151–155 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: AYY

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 59 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.4 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

AYY belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables