Laying and handling guide

LV armoured cables: laying and handling

Armoured and concentric conductor cables, 0.6/1 kV: BS 5467, BS 6724, BS 7846 (SWA) and NYCWY.

Every line names every source that states it and how it was seen; where sources disagree, each value is shown with its source. IEC, EN and HD documents and makers come first, national rules after them with their country.

Laying temperature and pre-warming

  • The limit is the temperature of the cable itself, not of the air: a drum stored in the cold stays cold after the air warms.Sources: HD 620 Part 1 A.4.12; HD 603 3-G, 5-G, 3-I, 4-B; Nexans 2021 p. 11 (read in the standard text)
  • Colder than its minimum: warm the whole drum for 1 to 2 days (at least 24 hours in HD 620 10-B). A full drum near the limit can take 20 to 30 hours to warm through (10-F).Sources: HD 620 Part 1 A.4.12; 10-F-20; 10-B-36 (read in the standard text)
  • Nexans: Warm at +10 °C or more for at least 24 hours, then unreel within 2 hours at about 20 m/min; below -5 °C outside, postpone the pull or warm the drums first.Sources: Nexans 2021 p. 11 (maker's document)
  • A cable stored below its minimum laying temperature takes no shocks, impacts, bending or twisting.Sources: HD 620 Part 1 A.3.1; HD 603 3-I 3.3; Nexans Belgium 2022 (read in the standard text)
  • HD 603 3-G, 5-G · HD 620 10-A, 10-C, 10-F: Cable temperature while laying and fitting accessories: at least -5 °C with a PVC sheath, -20 °C with a PE sheath; warm the cable when it is colder.Sources: HD 603 3-G-15 item 2; 5-G-15 item 2; HD 620 10-A-25 item 14; 10-C-26 item 14; 10-F-21 (read in the standard text)
  • Anixter: PVC and thermoplastic LSF turn brittle near 0 °C; elastomers stay flexible to -20 °C, but do not bend them to the minimum radius below -15 °C.Sources: Anixter Sec. 20 p. 20-43 (maker's document)

National rules

  • India IS 1255: Warm a cable colder than 3 °C, whatever its insulation, in a heated building or a hot-air tent for at least 24 hours to about 10 °C, and lay it swiftly.Sources: IS 1255 8.4, p. 26 (read in the standard text)
  • United Kingdom BS 6622, BS 5467, BS 7846: Cable and air above 0 °C for the previous 24 hours, or special precautions that keep the cable above 0 °C.Sources: BS 6622 C.1; BS 5467 B.2; BS 7846 A.7.2; HD 620 10-O-23; Anixter Sec. 20 p. 20-43 (read in the standard text)

Laying in winter? Pro checks your town and month against this limit. See Pro

Bending radius

  • IEC 60502-1: Gives no installation bending radius; the values below come from HD 603.Sources: IEC 60502-1 text searched (read in the standard text)
  • D is the cable's outer diameter. One controlled bend: a single bend next to a joint or termination, made by skilled workers over a template, the cable at or warmed to 30 °C.Sources: HD 620 Part 1 A.4.6; HD 603 3-G-16 (read in the standard text)
  • HD 603 3-G, 5-G: While laying 15 D single core, 12 D multicore; for one controlled bend 7.5 D and 6 D.Sources: HD 603 3-G-16, 5-G-16 (read in the standard text)
  • Prysmian UK: BS 5467, BS 6724, BS 7846: 8 D while laying.Sources: Prysmian UK p. 2 (maker's document)

National rules

  • India IS 1255: PVC and XLPE: single core 15 D up to 11 kV, 20 D above; multicore 12 D up to 1.1 kV, 15 D above. Cores at joints and terminations: more than 12 times the diameter over the insulation.Sources: IS 1255 5.3, Table 5, p. 14; 5.3.2 (read in the standard text)
  • Türkiye EKAT Çizelge-20: Three-core LV (XLPE or PVC) 12 D; three-core MV 15 D; armoured 15 D; single core 15 D.Sources: EKAT Madde 58 b) 9 (read in the standard text)
  • Türkiye TEDAŞ: As printed by HES Kablo: unarmoured LV 12 D single core, 10 D multicore; unarmoured MV 14 D and 12 D; armoured 15 D and 12 D. It differs from EKAT Çizelge-20.Sources: HES Kablo p. 388 (maker's document)
  • United Kingdom BS 5467, BS 6724: Installation radius: 6 D with circular copper conductors, 8 D with solid aluminium or shaped copper.Sources: BS 5467 Table B.1; BS 6724 Table B.1 (read in the standard text)
  • United Kingdom BS 7846: 8 D while laying.Sources: BS 7846 A.7.3 (read in the standard text)

Pulling force and method

  • On the conductors, with a pulling eye or head: at most 50 N/mm² for copper and 30 N/mm² for aluminium, over the main conductors' total section.Sources: HD 603 3-G-16 and the other guides to use; HD 620 Part 1 A.4.13 a; 10-C-26; IS 1255 5.4.2, p. 15; EKAT Madde 58 b) 10; Nexans 2021 p. 13; HES Kablo p. 391 (read in the standard text)
  • Gather all conductors in the pulling head and clamp them together, so the force spreads evenly.Sources: HD 603 3-I; EKAT Madde 58 b) 10 (read in the standard text)
  • A swivel between the cable grip and the pulling rope.Sources: HD 620 10-R item 15; Draka p. 6 (read in the standard text)
  • Watch the tension all through a machine pull and keep the record with the as-laid documents. Prysmian: a winch with a dynamometer, a preset maximum and automatic stop; Draka: without a tension record the maker may refuse a claim.Sources: HD 620 Part 1 A.4.4; HD 603 3-G 3.3; IS 1255 10.3.5; Prysmian 2024 p. 10; Nexans 2021 p. 16; Draka p. 8 (read in the standard text)
  • Rollers on straight runs every 2 to 4 m (Prysmian) or 3 to 4 m (Nexans for direct burial, IS 1255); at bends several rollers forming a radius larger than the minimum bending radius (IS 1255: corner rollers and at least three solid plates).Sources: HD 620 Part 1 A.4.4; HD 603 3-G 3.3; IS 1255 10.2.2, p. 30; Prysmian 2024 p. 10; Nexans 2021 p. 16, 17 (read in the standard text)
  • Sidewall pressure: the maker's limit, checked before the pull at every bend, roller and deflection point; too much tears the sheath.Sources: BS 7846 A.7.4 d); Nexans 2021 p. 17; Anixter Sec. 20 p. 20-44 (read in the standard text)
  • Guide the cable into a duct along its axis, with a bell mouth at the duct end, in one continuous arc without a reverse bend.Sources: BS 7846 A.7.4 f); IS 1255 6.3.4.4, 6.4.1; Nexans 2021 p. 17; Southwire 2005 p. 3 (read in the standard text)
  • Cable laid out on the ground goes down in a figure of eight, never in rings: rings twist it.Sources: IS 1255 10.2.4.6, p. 32; Draka p. 9; Nexans 2021 p. 19 (read in the standard text)
  • HD 603: On a cable grip: as on the conductors for unarmoured cables without a metal sheath (3-G, 5-G); 3 × D² N (3-I); 5 × D² N (3-L, 5-O, 5-P); at most 1000 N (4-B, 5-I, 6-A); at most 10 000 N (7-A, 7-B).Sources: HD 603 3-G-16, 3-I-20, 3-L-19, 4-B-18, 7-A-23, 7-B-20 (read in the standard text)

National rules

  • India IS 1255: On a stocking: 9 × D² N for armoured PVC or XLPE cables, 5 × D² N unarmoured, 3 × D² N for armoured paper cables. For armoured cables that is three times the HD 620 value.Sources: IS 1255 5.4.1, p. 15; HD 620 Part 1 A.4.13 c (read in the standard text)
  • India IS 1255: Expected winch force: 15 to 20 % of the cable's weight in a trench without large bends, 20 to 40 % with one or two 90° bends, 50 to 60 % with three, up to 100 % in ducts with bends totalling 360°.Sources: IS 1255 5.5, p. 16 (read in the standard text)
  • United Kingdom BS 5467, BS 7846: The maximum tension is the maker's value.Sources: BS 5467 Q.4.2; BS 7846 A.7.4 c), d) (read in the standard text)

Work out the pull for your route: the verdict is free, the numbers and the PDF come with Pro. Pull calculation in the cable designer · See Pro

Depth, cover and laying

  • Choose the way of laying and the bedding for the oversheath; trench walls smooth and free of stones.Sources: HD 620 Part 1 A.4.2 d), A.4.4; HD 603 3-G 1.2 d) (read in the standard text)
  • Single-core cables: all three phases of one system through the same steel pipe or hole; fixings must not form a magnetic ring round one core.Sources: HD 620 Part 1 A.4.9 b); HD 603 3-G 1.4; 3-L 5.1.3; IS 1255 6.3.4.6, 8.8.4; EKAT Madde 58 b) 3, 7 (read in the standard text)
  • Duct inner diameter at least 1.5 D in most HD sections and IS 1255, 1.5 to 2 D in HD 603 3-L, 5-O and 5-P, at least 1.4 D in the Italian sections; keep sand out of the duct.Sources: HD 603 3-G, 5-G, 3-L, 5-O, 5-P, 7-A; HD 620 10-A, 10-B, 10-C, 10-F, 10-I1, 10-R, 12-I; IS 1255 6.3.4.3, p. 18 (read in the standard text)

National rules

  • Australia and New Zealand AS/NZS 3000: Armoured cable buried direct 500 mm (gardens, footpaths); conduit 300 mm in gardens, 750 mm under driveways. Summarised by a supplier: check AS/NZS 3000.Sources: AS/NZS 3000 (Wilken) (secondary source)
  • France NF C 15-100, NF C 13-200: LV at least 0.50 m, HTA (MV) 0.80 m, 0.85 m under vehicle ways and pavements; a warning grid at least 0.20 m above the cable or its protection.Sources: Prysmian France pp. 1 to 2 (secondary source)
  • Germany HD 603 3-G, 5-G · HD 620 10-A, 10-C: At least 0.6 m deep, 0.8 m below roads; shallower only with other protection.Sources: HD 603 3-G-15 item 1.3, 5-G-15; HD 620 10-A-25 item 11, 10-C-26 item 11 (read in the standard text)
  • Hong Kong Code of Practice 25C(3)(a): Armoured or metal-sheathed cables only: at least 450 mm (category 1 and 3 circuits) or 750 mm (category 4); sand or fine soil at least one cable diameter below and 100 mm over, then cover tiles.Sources: Hong Kong CoP 25C(3)(a), p. 159 (read in the standard text)
  • India IS 1255: At least 0.75 m to the top of the cable for LV and control cables, 0.9 m for 3.3 to 11 kV, 1.05 m for 22 and 33 kV, 1.0 m at road and railway crossings; at least 75 mm of riddled soil or sand below and above, then tiles, bricks or slabs.Sources: IS 1255 6.3.1, 6.3.2, 6.3.6, pp. 16, 19 (read in the standard text)
  • Türkiye EKAT: At least 0.80 m under streets and squares, 0.60 m elsewhere, about 20 cm less with special protection where it cannot be avoided; road and rail crossings in pipes or channels, the top at least 1 m below the road surface or rail foot.Sources: EKAT Madde 58 b) 11, 16 (read in the standard text)
  • Türkiye EKAT: About 10 cm of sieved sand below and above the cable; brick, a concrete slab of at least 6 cm or a plastic cover over the sand along the whole route; a PE warning tape at least 10 cm wide about 30 cm above the cover.Sources: EKAT Madde 58 b) 13 (read in the standard text)
  • United Kingdom NJUG: Depth to the top of the cable: LV 450 mm under footways and verges, 600 mm under carriageways; HV 450 to 1200 mm and 750 to 1200 mm. Yellow marker tape directly above (HV: black and red legend, or concrete tiles).Sources: NJUG Table 1, p. 6 (read in the standard text)
Open groundSand bedWarning tape0.45 mNot found
Minimum cover: 0.45 m, United Kingdom: LV 450 mm footway or verge / 600 mm carriageway, surface to crown (Streetworks UK, NJUG Volume 1, Issue 5, 2018, Table 1 p. 6; read in the standard text). BS 5467 4x95 SWA 0,6/1 kV. To scale: the cover and the cable, Ø 39.7 mm. The sand bed, warning tape and duct are a picture only.

Drum handling

  • Keep the drum upright, its axis horizontal, in storage and in transport; never lay it flat on a flange.Sources: HD 620 Part 1 A.3.2.5, A.3.3.2; IS 1255 7.7, p. 25; Prysmian 2024; Reka (read in the standard text)
  • Never drop a drum. Without lifting gear, use a ramp of about 1:4 (IS 1255: 1:3 to 1:4) with ropes or a winch and a sand bed at the foot.Sources: HD 620 Part 1 A.3.3.3; HD 603 3-I 3.3; IS 1255 7.3, p. 24; Prysmian 2024 p. 6; Reka p. 6; Nexans 2021 p. 4 (read in the standard text)
  • Roll it only short distances on firm ground, in the direction of the arrow on the flange.Sources: HD 620 Part 1 A.3.3.4; HD 603 3-I, 3-L; IS 1255 7.4, p. 24; Prysmian 2024 p. 7; Nexans 2021 p. 3 (read in the standard text)
  • Store it on level, firm, well-drained ground and turn it 90° every 3 months.Sources: IS 1255 7.5, 7.6, pp. 24 to 25; Prysmian 2024 p. 8, 9; Nexans 2021 p. 8, 9; Prysmian Türkiye 3.3 (read in the standard text)
  • Leave the battens on until the cable is about to be laid: they keep off sun and knocks.Sources: HD 620 Part 1 A.3.2.5; BS 6622 D.5.2; IS 1255 7.8, p. 25; Nexans 2021 p. 11 (read in the standard text)
  • Cable ends sealed with caps in transport, storage and laying. A cap missing for over a month, or a wet end: cut back 300 mm, check for moisture and cap again.Sources: HD 620 Part 1 A.3.2.3, A.4.7; HD 603 3-I 3.2; BS 6622 C.3; BS 5467 B.4; BS 7846 A.7.4; IS 1255 7.2, p. 24; Nexans 2021 p. 7; Draka (read in the standard text)
  • Pay out tangentially, never over the flange, with the drum on an axle and jacks and braked. Top or bottom: IS 1255 says off the top; Southwire chooses by where the cable goes (the bottom into a floor conduit, the top into a tray); Nexans Belgium says the bottom, for safety.Sources: HD 620 Part 1 A.4.5; IS 1255 8.2, 8.3, 10.2; Southwire 2005 p. 2 to 3; Nexans Belgium FAQ; Prysmian 2024 p. 10; Draka p. 5, 9 (read in the standard text)
  • HD 620 10-A, 10-C, 10-K · HD 603 3-L: Flange over 1.0 m: the drum axis horizontal in transport; in HD 603 3-L, drums over 2.5 t.Sources: HD 620 10-A-24 item 6; HD 603 3-L; Prysmian 2024 (read in the standard text)

Sheath test after laying

  • HD 603 3-G, 5-G · HD 620 10-A, 10-C, 10-R: At most 3 kV d.c. on a PVC sheath, 5 kV d.c. on a PE sheath; faults usually show within 1 minute.Sources: HD 603 3-G 1.6, 5-G 1.6; HD 620 10-A 3.5, 10-C 3.5, 10-R 3.5 (read in the standard text)
  • Look the cable over before burying it, trace it with a locator afterwards, and check the end caps after the pull.Sources: HD 620 10-R-18 item 1; IS 1255 8.7, p. 27; Nexans 2021 p. 13; Draka p. 8 (read in the standard text)

National rules

  • India IS 1255: A d.c. test of the insulation after installation, 5 minutes, conductor to sheath: 3 kV (0.65/1.1 kV), 18 kV (6.35/11 kV), 37.5 kV (12.7/22 kV), 60 kV (19/33 kV). This goes against the HD 620 and BS 6622 advice not to test the insulation with d.c.Sources: IS 1255 14.2.4, Table 6, p. 60; HD 620 10-F, 10-K, 12-K; BS 6622 (read in the standard text)

Get the commissioning sheet for your own cable with Pro. See Pro

In the cable designer

Cable codes of this family

Terms on this page

Sources

Values as the sources print them. For a given job the cable's own standard, the maker's datasheet and the country's rules decide.