NA2XYH

NA2XYH is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); Y = Polyvinyl Chloride (PVC); H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NA2XYH 1x16 0.6/1 kV:

  • NA2XYH: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); Y = Polyvinyl Chloride (PVC); H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)
  • 1x16 0.6/1 kV: one core, aluminium 16 mm²; rated voltage 0.6/1 kV

Related cable types: NA2XH · NA2XY · NA2XRH · NA2XY-O · NA2XY-J · NA2XSH

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
AAluminium Conductor
2XCross-Linked Polyethylene (XLPE)
YPolyvinyl Chloride (PVC)
HHalogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.

What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).

What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).

What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

Fire behaviour (EU CPR)

  • Halogen-free compound (H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NA2XYH: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)NA2XH 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm
IndiaIS 7098 (Part 1)A2XZ 1x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm; this cable as built misses 1 of its rules
South AfricaSANS 1507-4no letters for this buildCloseSheath material LSZH → PVC; Inner covering / bedding material: only in the equivalent; Wire armour material: only in the equivalent; Overall diameter 9.1 → 12.5 mm

No equivalent in: BS 5467 (not in its cable tables, armoured cables only, asks another sheath compound); BS 6724 (not in its cable tables, armoured cables only); BS 7846 (not in its cable tables, armoured cables only).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NA2XYH as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.1 mm, about 110 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
SheathHalogen-free (LSZH)1.49.1

NA2XYH on a drum

The smallest drum that passes every check, for 9.1 mm and about 110 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1462 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG15 of 17141–145 kg

Barrel at least 20 × OD = 182 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NA2XYH

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 7.4 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

NA2XYH belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables