NA2XSH
NA2XSH is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of NA2XSH 1x240/25 12/20 kV:
NA2XSH: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)1x240/25 12/20 kV: one core, aluminium 240 mm²; rated voltage 12/20 kV
Related cable types: NA2XH · NA2XRH · NA2XSY · NA2XSEH · NA2XS · N2XSH
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
A | Aluminium Conductor |
2X | Cross-Linked Polyethylene (XLPE) |
S | Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores |
H | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.
What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).
What does s mean in a DIN VDE 0271/0276 power cables (Germany) cable code? s means Sector Shaped Conductor; or Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores.
What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
Fire behaviour (EU CPR)
Halogen-free compound (H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NA2XSH: equivalents in other countries
Shown for 1x240/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Netherlands | HD 620 S3 10-J | no letters for this build | Equivalent | Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 38.4 → 38.8 mm |
| International (IEC) | IEC 60502 | Al/XLPE/CWS/LSZH 1x240/25 12/20 kV (to IEC 60502-2) | Close | Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2.1 mm; Overall diameter 38.4 → 38 mm |
| HD 620 S3 10-L | no letters for this build | Close | Insulation screen (semicon) 0.6 → 0.8 mm; Sheath material LSZH → PVC; Sheath 2.5 → 2.2 mm; Overall diameter 38.4 → 38.2 mm | |
| Sweden | HD 620 S3 10-M | AXCQJ 1x240/35 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | Close | screen 25 → 35 mm² (HD 620 10-M Tables 1A, 2A, 3A); Sheath 2.5 → 2.2 mm; Overall diameter 38.4 → 37 mm; this cable as built misses 1 of its rules |
| Norway | HD 620 S3 10-K | no letters for this build | Close | screen 25 → 35 mm² (HD 620 10-K Table 1); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2.2 mm; Overall diameter 38.4 → 37.4 mm; this cable as built misses 1 of its rules |
| United Kingdom | HD 620 S3 10-O | no letters for this build | Close | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.6 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules |
| Spain | HD 620 S3 10-E1 | RHZ1-OL 12/20 kV 1 x 240 K Al + H16 | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.6 → 0.5 mm; Wire screen section 25 → 16 mm²; Sheath 2.5 → 3 mm; this cable as built misses 1 of its rules |
| Denmark | HD 620 S3 10-D | no letters for this build | Close | screen 25 → 35 mm² (HD 620 10-D Table 1); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 3 mm; Overall diameter 38.4 → 39.8 mm; this cable as built misses 2 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | Close | Insulation 5.5 → 4.8 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Sheath material LSZH → PE; Sheath 2.5 → 2.2 mm |
| Europe | HD 620 S3 10-P | no letters for this build | Close | Insulation screen (semicon) 0.6 → 0.8 mm; Wire screen material: not in the equivalent; Sheath material LSZH → PVC; Sheath 2.5 → 3 mm; this cable as built misses 1 of its rules |
| Spain | HD 620 S3 10-E2 | no letters for this build | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.6 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| India | IS 7098 (Part 2) | A2XY 1x240 12.7/22 kV | Close | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Wire screen material: not in the equivalent; this cable as built misses 1 of its rules |
| Italy | HD 620 S3 10-I1 | ARE4H5EX 12/20 kV 1 x 240 | Close | Insulation 5.5 → 4.31 mm; Wire screen material: not in the equivalent; Sheath material LSZH → PE; Sheath 2.5 → 2.2 mm; this cable as built misses 1 of its rules |
| HD 620 S3 10-G | no letters for this build | Close | Insulation 5.5 → 4.3 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Wire screen material: not in the equivalent; Sheath material LSZH → PE |
No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
NA2XSH as the cable designer builds it, 1x240/25 12/20 kV
Overall diameter 38.0 mm, about 1,770 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 19.6 |
| Insulation | XLPE | 5.5 | 30.6 |
| Insulation screen (semicon) | Semiconducting | 0.80 | 32.2 |
| Wire screen | Copper | 65 × 0.70 | 33.8 |
| Sheath | Halogen-free (LSZH) | 2.1 | 38.0 |
NA2XSH on a drum
The smallest drum that passes every check, for 38 mm and about 1,770 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 9 | 1,226–1,298 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 9 | 2,249–2,370 kg |
Barrel at least 25 × OD = 950 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NA2XSH
NA2XSH belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
- Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²
Typical; no maker or kit is named, and your kit's own sheet decides.
Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro
Work with NA2XSH
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.