NA2XY

NA2XY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); Y = Polyvinyl Chloride (PVC).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NA2XY 3x16 0.6/1 kV:

  • NA2XY: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); Y = Polyvinyl Chloride (PVC)
  • 3x16 0.6/1 kV: 3 cores, each aluminium 16 mm²; rated voltage 0.6/1 kV

Related cable types: NA2XY-O · NA2XY-J · NA2XYH · (N)A2XY-J(O) · (N)A2XY 1X300 · (N)A2XY 1X240

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
AAluminium Conductor
2XCross-Linked Polyethylene (XLPE)
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.

What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).

What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NA2XY dimensions and weight

Every NA2XY size

NA2XY: equivalents in other countries

Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502Al/XLPE/PVC 3x16 0,6/1 kV (to IEC 60502-1)Equivalentevery value the same
South AfricaSANS 1507-4no letters for this buildCloseInner covering / bedding material: not in the equivalent; Overall diameter 19.17 → 17.17 mm
IndiaIS 7098 (Part 1)A2XY 3x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NA2XY as the cable designer builds it, 3x16 0.6/1 kV

Overall diameter 19.2 mm, about 400 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP13.6
Inner covering / beddingPVC1.015.6
SheathPVC1.819.2

NA2XY on a drum

The smallest drum that passes every check, for 19.2 mm and about 400 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 11271–278 kg
1,000 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG12 of 14544–565 kg

Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NA2XY

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 7.4 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

NA2XY belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NA2XY

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

NA2XY compared

Related cables

More DIN VDE 0271/0276 power cables (Germany) designations

NA2XY