NA2XH
NA2XH is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of NA2XH 3x16 0.6/1 kV:
NA2XH: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)3x16 0.6/1 kV: 3 cores, each aluminium 16 mm²; rated voltage 0.6/1 kV
Related cable types: NA2XH-O · NA2XHY · N2XH · NA2XY · NA2XRH · NA2X
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
A | Aluminium Conductor |
2X | Cross-Linked Polyethylene (XLPE) |
H | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.
What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).
What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
Fire behaviour (EU CPR)
Halogen-free compound (H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NA2XH dimensions and weight
- NA2XH 4x50 SE 0.6/1 kV
- NA2XH 4x70 SE 0.6/1 kV
- NA2XH 4x95 SE 0.6/1 kV
- NA2XH 4x120 SE 0.6/1 kV
- NA2XH 4x150 SE 0.6/1 kV
- NA2XH 4x185 SE 0.6/1 kV
- NA2XH 4x240 SE 0.6/1 kV
- NA2XH 1x50 0.6/1 kV
- NA2XH 1x70 0.6/1 kV
- NA2XH 1x95 0.6/1 kV
- NA2XH 1x120 0.6/1 kV
- NA2XH 1x150 0.6/1 kV
- NA2XH 1x185 0.6/1 kV
- NA2XH 1x240 0.6/1 kV
- NA2XH 1x300 0.6/1 kV
NA2XH: equivalents in other countries
Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | Al/XLPE/LSZH 3x16 0,6/1 kV (to IEC 60502-1) | Equivalent | every value the same |
| India | IS 7098 (Part 1) | A2XZ 3x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding material: not in the equivalent; Sheath material LSZH → PVC; Overall diameter 19.17 → 17.17 mm |
No equivalent in: BS 5467 (armoured cables only, asks another sheath compound); BS 6724 (armoured cables only); BS 7846 (not in its cable tables, armoured cables only).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
NA2XH as the cable designer builds it, 3x16 0.6/1 kV
Overall diameter 19.2 mm, about 410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 13.6 | |
| Inner covering / bedding | Halogen-free (LSZH) | 1.0 | 15.6 |
| Sheath | Halogen-free (LSZH) | 1.8 | 19.2 |
NA2XH on a drum
The smallest drum that passes every check, for 19.2 mm and about 410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 11 | 276–283 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 14 | 554–575 kg |
Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NA2XH
NA2XH belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with NA2XH
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.