NA2XH 1x95 RM 0,6/1 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, NA2XH 1x95 RM 0,6/1 kV comes to an overall diameter of about 16.7 mm and a weight of about 410 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorAluminium 95 mm² RM, Ø 11.5 mmIEC 60228 class 2 compacted, middle of min / max
InsulationXLPE 1.1 mmIEC 60502-1:2004 Tables 5-7, nominal insulation thickness
Diameter over insulation13.7 mm
Overall diameter16.7 mm
Weight (approximate)410 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationXLPE1.113.7IEC 60502-1:2004 Tables 5-7, nominal insulation thicknessas manufacturers publish it, table not read
2SheathHalogen-free (LSZH)1.516.7IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Low voltage insulation (IEC 60502-1) is as manufacturers publish it; the table itself was not read. Sources and page numbers: research/mv-dimensions in the site repository.

Materials in this cable: Aluminium, XLPE, Halogen-free (LSZH)

Weight, by part

Conductors260 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths150 kg/km
Total410 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

NA2XH 1x95 RM 0,6/1 kV: equivalents in other countries

Shown for 1x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502Al/XLPE/LSZH 1x95 0,6/1 kV (to IEC 60502-1)EquivalentSheath 1.8 → 1.5 mm; Overall diameter 17.3 → 16.7 mm
IndiaIS 7098 (Part 1)no letters for this buildCloserated 0.635/1.1 kV (same Um 1.2 kV)

No equivalent in: BS 5467 (armoured cables only, asks another sheath compound); BS 6724 (armoured cables only); BS 7846 (not in its cable tables, armoured cables only).