AL/XLPE/LSZH
AL/XLPE/LSZH is a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable designation: AL = Aluminium Conductor; XLPE = Cross-Linked Polyethylene (XLPE); LSZH = Low Smoke Zero Halogen Compound.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of AL/XLPE/LSZH 3x16 0.6/1 kV:
AL/XLPE/LSZH: AL = Aluminium Conductor; XLPE = Cross-Linked Polyethylene (XLPE); LSZH = Low Smoke Zero Halogen Compound3x16 0.6/1 kV: 3 cores, each aluminium 16 mm²; rated voltage 0.6/1 kV
Related cable types: XLPE/LSZH
Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice)
| Symbol | Meaning |
|---|---|
AL | Aluminium Conductor |
XLPE | Cross-Linked Polyethylene (XLPE) |
LSZH | Low Smoke Zero Halogen Compound |
How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code
How to read a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code
A Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designation (UK / International) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 119 symbols for this system.
What does AL mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? AL means Aluminium Conductor.
What does XLPE mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? XLPE means Cross-Linked Polyethylene (XLPE).
What does LSZH mean in a Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) cable code? LSZH means Low Smoke Zero Halogen Compound.
Fire behaviour (EU CPR)
Halogen-free compound (LSZH). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
AL/XLPE/LSZH: equivalents in other countries
Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | NA2XH 3x16 RM 0,6/1 kV | Equivalent | every value the same |
| India | IS 7098 (Part 1) | A2XZ 3x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding material LSZH → PVC; Inner covering / bedding 1 → 0.8 mm; Sheath material LSZH → PVC; Sheath 1.8 → 1.6 mm |
No equivalent in: BS 5467 (armoured cables only, asks another sheath compound); BS 6724 (armoured cables only); BS 7846 (not in its cable tables, armoured cables only).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
AL/XLPE/LSZH as the cable designer builds it, 3x16 0.6/1 kV
Overall diameter 19.2 mm, about 410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 13.6 | |
| Inner covering / bedding | Halogen-free (LSZH) | 1.0 | 15.6 |
| Sheath | Halogen-free (LSZH) | 1.8 | 19.2 |
AL/XLPE/LSZH on a drum
The smallest drum that passes every check, for 19.2 mm and about 410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 11 | 276–283 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 14 | 554–575 kg |
Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AL/XLPE/LSZH
AL/XLPE/LSZH belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with AL/XLPE/LSZH
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More Layer-list designation (CU/XLPE/SWA/PVC style, IEC and BS practice) designations