2XS(F)2Y

2XS(F)2Y is a DIN VDE 0271/0276 power cables (Germany) cable designation: 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; (F) = Longitudinal Water Resistant Tape; 2Y = Polyethylene (PE).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of 2XS(F)2Y 1x95/16 12/20 kV:

  • 2XS(F)2Y: 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; (F) = Longitudinal Water Resistant Tape; 2Y = Polyethylene (PE)
  • 1x95/16 12/20 kV: one core, copper 95 mm²; rated voltage 12/20 kV

Related cable types: (N)2XS(F)2Y · A2XS(F)2Y · (N)A2XS(F)2Y

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
2XCross-Linked Polyethylene (XLPE)
SCopper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores
(F)Longitudinal Water Resistant Tape
2YPolyethylene (PE)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).

What does s mean in a DIN VDE 0271/0276 power cables (Germany) cable code? s means Sector Shaped Conductor; or Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores.

What does (F) mean in a DIN VDE 0271/0276 power cables (Germany) cable code? (F) means Longitudinal Water Resistant Tape.

What does 2Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2Y means Polyethylene (PE).

Fire behaviour (EU CPR)

  • PE sheath (2Y).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

N2XS(F)2Y dimensions and weight

Every N2XS(F)2Y size

2XS(F)2Y: equivalents in other countries

Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
DenmarkHD 620 S3 10-Dno letters for this buildClosescreen 16 → 25 mm² (HD 620 10-D Table 1); this cable as built misses 1 of its rules
GermanyHD 620 S3 10-C (DIN VDE 0276-620)N2XS(F)2Y 1x95 RM/16 12/20 kVCloseInsulation screen (semicon) 0.8 → 0.6 mm; Sheath 1.9 → 2.5 mm; Overall diameter 31.9 → 32.7 mm; this cable as built misses 2 of its rules
NorwayHD 620 S3 10-KTXSE 24 kV 1 x 95 mm2 (provisional code designation of HD 620 10-K Table 4; X is not explained in the standard)Closescreen 16 → 25 mm² (HD 620 10-K Table 1); Overall diameter 31.9 → 31.1 mm; this cable as built misses 1 of its rules
NetherlandsHD 620 S3 10-JYMeKrvaslqwd 12/20 kV 1x95 rs +as25 (key read from a maker (Nedkab), the NEN text not seen)Closescreen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.9 → 2.5 mm; Overall diameter 31.9 → 33.1 mm; this cable as built misses 1 of its rules
SwedenHD 620 S3 10-MFXCLJ 1x95/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ); the letters do not say the longitudinal water block (makers add LT or PT))Closescreen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 31.9 → 30.7 mm; this cable as built misses 2 of its rules
HD 620 S3 10-Lno letters for this buildCloseSwelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Sheath material PE → PVC; Overall diameter 31.9 → 30.7 mm
EuropeHD 620 S3 10-Nno letters for this buildCloseInsulation 5.5 → 4.8 mm; Swelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Sheath 1.9 → 1.8 mm
United KingdomHD 620 S3 10-Ono letters for this buildCloserated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Swelling tape (water block) material: not in the equivalent; this cable as built misses 1 of its rules
HD 620 S3 10-Gno letters for this buildCloseInsulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 1.8 mm; Tape screen material: only in the equivalent
EuropeHD 620 S3 10-Pno letters for this buildCloseSwelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Sheath material PE → PVC; this cable as built misses 1 of its rules
IndiaIS 7098 (Part 2)2X2Y 1x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3)Closerated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Swelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules

No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

2XS(F)2Y as the cable designer builds it, 1x95/16 12/20 kV

Overall diameter 31.9 mm, about 1,590 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6012.7
InsulationXLPE5.523.7
Insulation screen (semicon)Semiconducting0.8025.3
Swelling tape (water block)Swelling0.3025.9
Wire screenCopper42 × 0.7027.5
Swelling tape (water block)Swelling0.3028.1
SheathPE1.931.9

2XS(F)2Y on a drum

The smallest drum that passes every check, for 31.9 mm and about 1,590 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG7 of 111,071–1,104 kg
1,000 mKTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG11 of 111,931–2,003 kg

Barrel at least 25 × OD = 798 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: 2XS(F)2Y

2XS(F)2Y belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Accessories for this cable

Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).

  • Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
  • Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
  • Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
  • Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
  • Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
  • Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²

Typical; no maker or kit is named, and your kit's own sheet decides.

Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro

Work with 2XS(F)2Y