NA2XSEYRGY

NA2XSEYRGY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); SE = Copper Screen, Over Individual Core; Y = Polyvinyl Chloride (PVC); R = Round Steel Wire; G = Helical Galvanized Steel Tape; Y = Polyvinyl Chloride (PVC).

1 coding system recognises this code

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
AAluminium Conductor
2XCross-Linked Polyethylene (XLPE)
SECopper Screen, Over Individual Core
YPolyvinyl Chloride (PVC)
RRound Steel Wire
GHelical Galvanized Steel Tape
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NA2XSEYRGY as the cable designer builds it, 3x95/16 12/20 kV

Overall diameter 78.3 mm, about 9,240 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6012.7
InsulationXLPE5.523.7
Insulation screen (semicon)Semiconducting0.8025.3
Wire screenCopper42 × 0.7026.9
FillerPP58.0
Inner covering / beddingPVC1.661.2
SheathPVC1.864.8
Wire armourSteel65 × 3.1571.1
Tape armourSteel0.2071.5
SheathPVC3.478.3

NA2XSEYRGY on a drum

The smallest drum that passes every check, for 78.3 mm and about 9,240 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 82 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG5 of 55,795–5,860 kg
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 20 × OD = 1,565 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NA2XSEYRGY

NA2XSEYRGY belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NA2XSEYRGY

Related cables

More DIN VDE 0271/0276 power cables (Germany) designations