NA2XSEY

NA2XSEY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); SE = Copper Screen, Over Individual Core; Y = Polyvinyl Chloride (PVC).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NA2XSEY 3x95 12/20 kV:

  • NA2XSEY: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); SE = Copper Screen, Over Individual Core; Y = Polyvinyl Chloride (PVC)
  • 3x95 12/20 kV: 3 cores, each aluminium 95 mm²; rated voltage 12/20 kV

Related cable types: NA2XSEYRY · NA2XS2Y · NA2XSY · NA2XSEH · NA2XS(F)Y

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
AAluminium Conductor
2XCross-Linked Polyethylene (XLPE)
SECopper Screen, Over Individual Core
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.

What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).

What does SE mean in a DIN VDE 0271/0276 power cables (Germany) cable code? SE means Copper Screen, Over Individual Core; or Sector-Shaped Solid Conductor, IEC 60228 Class 1 (size field).

What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NA2XSEY: equivalents in other countries

Shown for 3x95 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
NetherlandsHD 620 S3 10-Jno letters for this buildEquivalentevery value the same
DenmarkHD 620 S3 10-Dno letters for this buildEquivalentevery value the same
NorwayHD 620 S3 10-Kno letters for this buildEquivalentOverall diameter 64.58 → 62.85 mm
SwedenHD 620 S3 10-MAXCKJ 3x95 12/20 (24) kV (NKT writes a near build without the C (AXLJ))CloseInsulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 64.58 → 61.99 mm; this cable as built misses 1 of its rules
IndiaIS 7098 (Part 2)A2XY 3x95 12.7/22 kVCloserated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Inner covering / bedding 1.6 → 0.7 mm; Sheath 3 → 3.2 mm; this cable as built misses 2 of its rules

No equivalent in: HD 620 S3 10-C (DIN VDE 0276-620) (no three-core cable at this voltage); BS 6622 (armoured cables only); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change); HD 620 S3 10-G (the size, cores or voltage would change); HD 620 S3 10-L (the size, cores or voltage would change); HD 620 S3 10-N (the size, cores or voltage would change); HD 620 S3 10-O (the size, cores or voltage would change); HD 620 S3 10-P (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NA2XSEY as the cable designer builds it, 3x95 12/20 kV

Overall diameter 64.6 mm, about 3,880 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6012.7
InsulationXLPE5.523.7
Insulation screen (semicon)Semiconducting0.8025.3
Tape screenCopper0.2025.7
FillerPP55.4
Inner covering / beddingPVC1.658.6
SheathPVC3.064.6

NA2XSEY on a drum

The smallest drum that passes every check, for 64.6 mm and about 3,880 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 68 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG5 of 73,115–3,180 kg
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 20 × OD = 1,292 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NA2XSEY

NA2XSEY belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Accessories for this cable

Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).

  • Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
  • Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
  • Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
  • Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
  • Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
  • Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²

The kits are single core: on this three core cable one goes on each core.

Typical; no maker or kit is named, and your kit's own sheet decides.

Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro

Work with NA2XSEY