N2XRY
N2XRY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; 2X = Cross-Linked Polyethylene (XLPE); R = Round Steel Wire; Y = Polyvinyl Chloride (PVC).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of N2XRY 4x16 0.6/1 kV:
N2XRY: N = VDE Standard; 2X = Cross-Linked Polyethylene (XLPE); R = Round Steel Wire; Y = Polyvinyl Chloride (PVC)4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
2X | Cross-Linked Polyethylene (XLPE) |
R | Round Steel Wire |
Y | Polyvinyl Chloride (PVC) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).
What does R mean in a DIN VDE 0271/0276 power cables (Germany) cable code? R means Round Steel Wire.
What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
N2XRY: equivalents in other countries
Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | N2XYRY 4x16 RM 0,6/1 kV | Close | this cable as built misses 1 of its rules |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding 1 → 1.2 mm; Sheath 1.2 → 1.7 mm; Wire armour wire diameter 1.6 → 1.25 mm; Sheath material: not in the equivalent |
| United Kingdom | BS 5467 | Cu/XLPE/PVC/SWA/PVC 4x16 0,6/1 kV (to BS 5467) | Close | built the British way: the armour on an extruded bedding, no separation sheath; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm; Wire armour wire diameter 1.6 → 1.25 mm |
| India | IS 7098 (Part 1) | 2XWY 4x16 1100 V | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm |
No equivalent in: BS 6724 (asks another sheath compound); BS 7846 (asks another sheath compound).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
N2XRY as the cable designer builds it, 4x16 0.6/1 kV
Overall diameter 26.4 mm, about 1,680 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Filler | PP | 15.2 | |
| Inner covering / bedding | PVC | 1.0 | 17.2 |
| Sheath | PVC | 1.2 | 19.6 |
| Wire armour | Steel | 40 × 1.60 | 22.8 |
| Sheath | PVC | 1.8 | 26.4 |
N2XRY on a drum
The smallest drum that passes every check, for 26.4 mm and about 1,680 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 10 | 984–1,005 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 11 of 14 | 1,956–1,989 kg |
Barrel at least 15 × OD = 396 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: N2XRY
N2XRY belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with N2XRY
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.