NYBY
NYBY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; Y = Polyvinyl Chloride (PVC); B = Steel Tape Armour; Y = Polyvinyl Chloride (PVC).
4 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of NYBY 4x16 0.6/1 kV:
NYBY: N = VDE Standard; Y = Polyvinyl Chloride (PVC); B = Steel Tape Armour; Y = Polyvinyl Chloride (PVC)4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
Y | Polyvinyl Chloride (PVC) |
B | Steel Tape Armour |
Y | Polyvinyl Chloride (PVC) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
TS 621 / TSE (Turkey)
| Symbol | Meaning |
|---|---|
N | Cable Resistant To Light & Normal Mechanical Load For Fixed Installation |
Y | Flat Conductor |
B | Fine-Wired For Fixed Installations-Class 5 |
Y | Flat Conductor |
DIN VDE 0250 cords, control and special cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
B | Lead Sheath |
Y | Polyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General |
How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
N | Nylon Jacket |
Y | Polyethylene (PE) Or Polyolefin |
B | Polypropylene (PP) |
Y | Polyethylene (PE) Or Polyolefin |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).
What does B mean in a DIN VDE 0271/0276 power cables (Germany) cable code? B means Steel Tape Armour.
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NYBY: equivalents in other countries
Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 3-G (DIN VDE 0276-603) | NYYBY 4x16 RM 0,6/1 kV | Close | this cable as built misses 1 of its rules |
| India | IS 1554 (Part 1) | YWY 4x16 1100 V | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
NYBY as the cable designer builds it, 4x16 0.6/1 kV
Overall diameter 25.5 mm, about 1,270 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Filler | PP | 16.7 | |
| Inner covering / bedding | PVC | 1.0 | 18.7 |
| Sheath | PVC | 1.2 | 21.1 |
| Tape armour | Steel | 0.40 | 21.9 |
| Sheath | PVC | 1.8 | 25.5 |
NYBY on a drum
The smallest drum that passes every check, for 25.5 mm and about 1,270 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 11 | 779–800 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 10 of 14 | 1,546–1,579 kg |
Barrel at least 15 × OD = 382 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NYBY
NYBY belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables
Terms on this page: steel tape armour