NYBY

NYBY is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; Y = Polyvinyl Chloride (PVC); B = Steel Tape Armour; Y = Polyvinyl Chloride (PVC).

4 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NYBY 4x16 0.6/1 kV:

  • NYBY: N = VDE Standard; Y = Polyvinyl Chloride (PVC); B = Steel Tape Armour; Y = Polyvinyl Chloride (PVC)
  • 4x16 0.6/1 kV: 4 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: NYY · NYCY · NYRY · NySy · Nygby

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC)
BSteel Tape Armour
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

TS 621 / TSE (Turkey)

SymbolMeaning
NCable Resistant To Light & Normal Mechanical Load For Fixed Installation
YFlat Conductor
BFine-Wired For Fixed Installations-Class 5
YFlat Conductor

How to read a TS 621 / TSE (Turkey) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
BLead Sheath
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
NNylon Jacket
YPolyethylene (PE) Or Polyolefin
BPolypropylene (PP)
YPolyethylene (PE) Or Polyolefin

How to read a China (GB / JB/T / MT cable model codes) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does Y mean in a DIN VDE 0271/0276 power cables (Germany) cable code? Y means Polyvinyl Chloride (PVC).

What does B mean in a DIN VDE 0271/0276 power cables (Germany) cable code? B means Steel Tape Armour.

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NYBY: equivalents in other countries

Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYYBY 4x16 RM 0,6/1 kVClosethis cable as built misses 1 of its rules
IndiaIS 1554 (Part 1)YWY 4x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

NYBY as the cable designer builds it, 4x16 0.6/1 kV

Overall diameter 25.5 mm, about 1,270 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
FillerPP16.7
Inner covering / beddingPVC1.018.7
SheathPVC1.221.1
Tape armourSteel0.4021.9
SheathPVC1.825.5

NYBY on a drum

The smallest drum that passes every check, for 25.5 mm and about 1,270 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 11779–800 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 141,546–1,579 kg

Barrel at least 15 × OD = 382 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NYBY

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 4.2 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

NYBY belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables

Terms on this page: steel tape armour

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NYBY

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

NYBY compared

Related cables

More DIN VDE 0271/0276 power cables (Germany) designations

NYBY