A2XFLH is a DIN VDE 0271/0276 power cables (Germany) cable designation: A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); FL = Longitudinal & Radial Water Resistant Tape; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of A2XFLH 1x16 0.6/1 kV:
A2XFLH: A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); FL = Longitudinal & Radial Water Resistant Tape; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)1x16 0.6/1 kV: one core, aluminium 16 mm²; rated voltage 0.6/1 kV
Related cable types: A2XFY · A2XS(F)H · A2XS(FL)Y · A2X(FL)2Y · N2X(FL)Y · N2XFGH
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
A | Aluminium Conductor |
2X | Cross-Linked Polyethylene (XLPE) |
FL | Longitudinal & Radial Water Resistant Tape |
H | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)
| Symbol | Meaning |
|---|---|
A | Outdoor Cable |
2X | Cross-Linked Polyethylene (XLPE) |
F | Jelly Compound |
L | Aluminium Sheath, Pressed Or Welded, Smooth |
H | Low Smoke Zero Halogen Compound |
How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does A mean in a DIN VDE 0271/0276 power cables (Germany) cable code? A means Aluminium Conductor.
What does 2X mean in a DIN VDE 0271/0276 power cables (Germany) cable code? 2X means Cross-Linked Polyethylene (XLPE).
What does FL mean in a DIN VDE 0271/0276 power cables (Germany) cable code? FL means Longitudinal & Radial Water Resistant Tape.
What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
Fire behaviour (EU CPR)
Halogen-free compound (H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
A2XFLH: equivalents in other countries
Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | NA2X(FL)H 1x16 RM 0,6/1 kV | Equivalent | every value the same |
| India | IS 7098 (Part 1) | A2XZ 1x16 1100 V (the code letters of IS 7098 (Part 1):2025 cl. 18.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Laminate (radial water block) material: not in the equivalent; Overall diameter 10.3 → 9.9 mm |
| South Africa | SANS 1507-4 | no letters for this build | Close | Laminate (radial water block) material: not in the equivalent; Sheath material LSZH → PVC; Sheath 1.8 → 1.4 mm; Inner covering / bedding material: only in the equivalent |
No equivalent in: BS 5467 (not in its cable tables, armoured cables only, asks another sheath compound); BS 6724 (not in its cable tables, armoured cables only); BS 7846 (not in its cable tables, armoured cables only).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
A2XFLH as the cable designer builds it, 1x16 0.6/1 kV
Overall diameter 10.3 mm, about 140 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Laminate (radial water block) | Aluminium | 0.20 | 6.7 |
| Sheath | Halogen-free (LSZH) | 1.8 | 10.3 |
A2XFLH on a drum
The smallest drum that passes every check, for 10.3 mm and about 140 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 13 of 13 | 77 kg |
| 1,000 m | KTG 9 (900 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 18 | 187–191 kg |
Barrel at least 20 × OD = 206 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: A2XFLH
A2XFLH belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables