(N)HXH

(N)HXH is a DIN VDE 0271/0276 power cables (Germany) cable designation: (N) = Similar To VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of (N)HXH 3x16 0.6/1 kV:

  • (N)HXH: (N) = Similar To VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)
  • 3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: NHXHM-J · NHXH E90 · Nhxh j · nhxh fe

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
(N)Similar To VDE Standard
HXHalogen-Free Materials
HHalogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
(N)Similar To VDE Standard
HXCross-Linked Halogen-Free Polymer Compound
HHalogen-Free Compound (Insulation Or Sheath)

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does (N) mean in a DIN VDE 0271/0276 power cables (Germany) cable code? (N) means Similar To VDE Standard.

What does HX mean in a DIN VDE 0271/0276 power cables (Germany) cable code? HX means Halogen-Free Materials.

What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

Fire behaviour (EU CPR)

  • Halogen-free compound (HX, H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

(N)HXH as the cable designer builds it, 3x16 0.6/1 kV

Overall diameter 19.2 mm, about 740 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationHalogen-free (LSZH)0.706.3
FillerPP13.6
Inner covering / beddingHalogen-free (LSZH)1.015.6
SheathHalogen-free (LSZH)1.819.2

(N)HXH on a drum

The smallest drum that passes every check, for 19.2 mm and about 740 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 11441–448 kg
1,000 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG12 of 14884–905 kg

Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: (N)HXH

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with (N)HXH

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More DIN VDE 0271/0276 power cables (Germany) designations

(N)HXH