NHXH
NHXH is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
8 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of NHXH 3x16 0.6/1 kV:
NHXH: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV
DIN VDE 0271/0276 power cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
HX | Halogen-Free Materials |
H | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
DIN VDE 0250 cords, control and special cables (Germany)
| Symbol | Meaning |
|---|---|
N | VDE Standard |
HX | Cross-Linked Halogen-Free Polymer Compound |
H | Halogen-Free Compound (Insulation Or Sheath) |
How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
NH | Fire Resistant |
X | Natural Or Styrene-Butadiene Rubber |
H | Rubber Sheath; Chlorosulphonated Polyethylene (CSM) Sheath In Marine Cables |
How to read a China (GB / JB/T / MT cable model codes) cable code
NEC Article 310 (US building wire, NFPA 70)
| Symbol | Meaning |
|---|---|
N | Nylon Jacket |
H | 75°C Insulation |
X | Cross-Linked Polymer Insulation |
H | 75°C Insulation |
How to read a NEC Article 310 (US building wire, NFPA 70) cable code
NEC Article 402 (US fixture wires, NFPA 70)
| Symbol | Meaning |
|---|---|
N | Nylon Jacket |
H | 75°C Heat-Resistant Insulation (After R Or FF); ECTFE Insulation (First Letter, HF / HFF) |
X | Cross-Linked Polyolefin Insulation |
H | 75°C Heat-Resistant Insulation (After R Or FF); ECTFE Insulation (First Letter, HF / HFF) |
How to read a NEC Article 402 (US fixture wires, NFPA 70) cable code
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
N | Impregnated Paper |
H | Chlorosulphonated Polyethylene (CSP) (Nexans key: or CPE) |
X | No Armour |
H | Chlorosulphonated Polyethylene (CSP) (Nexans key: or CPE) |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
ZN-TF-500 (Poland, MV cables)
| Symbol | Meaning |
|---|---|
N | Low Smoke Zero Halogen Compound |
H | Cable With Radial Field (Screened Cores, Medium Voltage) |
X | Polyethylene (PE) Sheath |
H | Cable With Radial Field (Screened Cores, Medium Voltage) |
Swiss cable codes (ASE/SEV wire codes and power cable codes)
| Symbol | Meaning |
|---|---|
N | Halogen-Free Thermoplastic Sheath (PE Only) |
H | Cable With Radial Electric Field (Höchstädter Type) |
X | Cross-Linked Polyethylene (XLPE) |
H | Cable With Radial Electric Field (Höchstädter Type) |
How to read a Swiss cable codes (ASE/SEV wire codes and power cable codes) cable code
How to read a DIN VDE 0271/0276 power cables (Germany) cable code
A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.
What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.
What does HX mean in a DIN VDE 0271/0276 power cables (Germany) cable code? HX means Halogen-Free Materials.
What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).
Fire behaviour (EU CPR)
Halogen-free compound (HX, H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NHXH as the cable designer builds it, 3x16 0.6/1 kV
Overall diameter 19.2 mm, about 740 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | Halogen-free (LSZH) | 0.70 | 6.3 |
| Filler | PP | 13.6 | |
| Inner covering / bedding | Halogen-free (LSZH) | 1.0 | 15.6 |
| Sheath | Halogen-free (LSZH) | 1.8 | 19.2 |
NHXH on a drum
The smallest drum that passes every check, for 19.2 mm and about 740 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 11 | 441–448 kg |
| 1,000 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 14 | 884–905 kg |
Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NHXH
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²