NHXH

NHXH is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

8 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NHXH 3x16 0.6/1 kV:

  • NHXH: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)
  • 3x16 0.6/1 kV: 3 cores, each copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: NHXHM-J · NHXH E90 · Nhxh j · nhxh fe

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
HXHalogen-Free Materials
HHalogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
HXCross-Linked Halogen-Free Polymer Compound
HHalogen-Free Compound (Insulation Or Sheath)

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
NHFire Resistant
XNatural Or Styrene-Butadiene Rubber
HRubber Sheath; Chlorosulphonated Polyethylene (CSM) Sheath In Marine Cables

How to read a China (GB / JB/T / MT cable model codes) cable code

NEC Article 310 (US building wire, NFPA 70)

SymbolMeaning
NNylon Jacket
H75°C Insulation
XCross-Linked Polymer Insulation
H75°C Insulation

How to read a NEC Article 310 (US building wire, NFPA 70) cable code

NEC Article 402 (US fixture wires, NFPA 70)

SymbolMeaning
NNylon Jacket
H75°C Heat-Resistant Insulation (After R Or FF); ECTFE Insulation (First Letter, HF / HFF)
XCross-Linked Polyolefin Insulation
H75°C Heat-Resistant Insulation (After R Or FF); ECTFE Insulation (First Letter, HF / HFF)

How to read a NEC Article 402 (US fixture wires, NFPA 70) cable code

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
NImpregnated Paper
HChlorosulphonated Polyethylene (CSP) (Nexans key: or CPE)
XNo Armour
HChlorosulphonated Polyethylene (CSP) (Nexans key: or CPE)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

ZN-TF-500 (Poland, MV cables)

SymbolMeaning
NLow Smoke Zero Halogen Compound
HCable With Radial Field (Screened Cores, Medium Voltage)
XPolyethylene (PE) Sheath
HCable With Radial Field (Screened Cores, Medium Voltage)

How to read a ZN-TF-500 (Poland, MV cables) cable code

Swiss cable codes (ASE/SEV wire codes and power cable codes)

SymbolMeaning
NHalogen-Free Thermoplastic Sheath (PE Only)
HCable With Radial Electric Field (Höchstädter Type)
XCross-Linked Polyethylene (XLPE)
HCable With Radial Electric Field (Höchstädter Type)

How to read a Swiss cable codes (ASE/SEV wire codes and power cable codes) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does HX mean in a DIN VDE 0271/0276 power cables (Germany) cable code? HX means Halogen-Free Materials.

What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

Fire behaviour (EU CPR)

  • Halogen-free compound (HX, H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

NHXH as the cable designer builds it, 3x16 0.6/1 kV

Overall diameter 19.2 mm, about 740 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationHalogen-free (LSZH)0.706.3
FillerPP13.6
Inner covering / beddingHalogen-free (LSZH)1.015.6
SheathHalogen-free (LSZH)1.819.2

NHXH on a drum

The smallest drum that passes every check, for 19.2 mm and about 740 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 10 (1000 mm flange), wood KTG drums (Europe), Bayka, KTG9 of 11441–448 kg
1,000 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG12 of 14884–905 kg

Barrel at least 15 × OD = 288 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NHXH

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²