NHXH FE

NHXH FE is a DIN VDE 0271/0276 power cables (Germany) cable designation: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter); FE = Insulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180.

3 coding systems recognise this code

Standard, worked reading and related types

Worked reading of NHXH FE:

  • NHXH FE: N = VDE Standard; HX = Halogen-Free Materials; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter); FE = Insulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180

Related cable types: N2XHFE · NHXH · NHXHM-J · N2XCH-FE · N2XH FE1 · Nhxh j

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
HXHalogen-Free Materials
HHalogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter)
FEInsulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
HXCross-Linked Halogen-Free Polymer Compound
HHalogen-Free Compound (Insulation Or Sheath)
FEInsulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
NHFire Resistant
XNatural Or Styrene-Butadiene Rubber
HRubber Sheath; Chlorosulphonated Polyethylene (CSM) Sheath In Marine Cables
FChloroprene Rubber
ELow Smoke Zero Halogen Compound

How to read a China (GB / JB/T / MT cable model codes) cable code

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

A DIN VDE 0271/0276 power cables (Germany) designation (Germany) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 51 symbols for this system.

What does N mean in a DIN VDE 0271/0276 power cables (Germany) cable code? N means VDE Standard.

What does HX mean in a DIN VDE 0271/0276 power cables (Germany) cable code? HX means Halogen-Free Materials.

What does h mean in a DIN VDE 0271/0276 power cables (Germany) cable code? h means Hollow Circular Conductor; or Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

What does FE mean in a DIN VDE 0271/0276 power cables (Germany) cable code? FE means Insulation Integrity In Fire (Isolationserhalt) For The Time Written After It, E.g. FE180 = 180 Min.

Fire behaviour (EU CPR)

  • Halogen-free compound (HX, H). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

  • Fire resistant (FE): the circuit keeps working in a fire. That is circuit integrity, classified apart from reaction to fire (EN 13501-3: P and PH classes, 15 to 120 min). It gives no reaction-to-fire class; that one is declared on its own.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Not equivalent, because

IEC 60331 ≠ BS 6387 (C, W, Z) ≠ BS 8491 ≠ EN 50200 (PH) ≠ DIN 4102-12 (E30, E60, E90) ≠ UL 2196

Not equivalent, because Flame or furnace, temperature, mechanical shock, water and what is tested (a cable alone, or a cable with its supports) all differ: a time or class from one test says nothing about another.

IEC 60331

  • Parts 1 and 2: a flame of at least 830 °C with mechanical shock; part 1 for cables over 20 mm, part 2 up to 20 mm; up to 0.6/1 kV. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)
  • Parts 11 and 21: fire alone, at least 750 °C. Sources: IEC 60331-11:1999+A1:2009 (edition 1.1), 5.2 p. 7, Annex A p. 13; IEC 60331-21:1999, cl. 7 and 8, pp. 13 to 15 (read in the standard)
  • Pass: the circuit keeps working for the stated time. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)

BS 6387 (C, W, Z)

  • C: 950 °C for 3 h. W: 650 °C for 15 min, then 15 min with water. Z: 950 °C with a shock every 30 s for 15 min. CWZ: all three passed. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)
  • Cables up to 600/1000 V and 20 mm diameter. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)

BS 8491

EN 50200 (PH)

  • 830 °C with a shock every 5 min, cables up to 20 mm; Annex E adds a water spray. Sources: BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)
  • Classes PH15, PH30, PH60, PH90, PH120 (EN 13501-3). Sources: EN 13501-3:2005+A1:2009 with draft A2 (cover September 2013), cl 4.3 p. 7; cl 6.3 p. 9; cl 7.2.4.4, 7.2.5.4 pp. 16-17; cl 7.2.6.2 p. 18 (read in a draft); BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)

DIN 4102-12 (E30, E60, E90)

  • The cable with its supports in a furnace on the standard temperature curve, at up to 400 V; E30, E60 and E90 hold only for the support system tested. Sources: Datwyler (N)HXCH FE180 E90 datasheet (maker's catalogue)

UL 2196

  • A furnace on the ASTM E119 time-temperature curve (NFPA 262 Annex A names it for UL 2196). Sources: NFPA 262:2023 (NFPA free access), Annex A, A.1.1.1 (read in the standard)
  • Ratings up to 2 h, with a hose stream after the fire. Sources: research: equivalents map F5 (UL 2196 not read) (typical practice)