TECK90

TECK90 is a CSA (Canada) cable designation: TECK = Armoured cable with inner and outer PVC jackets (trade name of the type); 90 = Maximum conductor temperature 90 C; TECK90 = Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 174.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: CSA C22.2 No. 131: Type TECK 90 cable. How the values are sourced

Worked reading of TECK90 3/C 2 AWG, 1000 V:

  • TECK90: TECK = Armoured cable with inner and outer PVC jackets (trade name of the type); 90 = Maximum conductor temperature 90 C; TECK90 = Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 174
  • 3/C 2 AWG, 1000 V: 3 cores, each copper 2 AWG (33.6 mm²); rated voltage 1000 V

CSA (Canada)

SymbolMeaning
TECKArmoured cable with inner and outer PVC jackets (trade name of the type)
90Maximum conductor temperature 90 C
TECK90Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 174

What is TECK90 cable?

TECK90: Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. Rating: 600 V, 1000 V or 5 kV, 90 C, FT4. Standard: CSA C22.2 No. 131 and No. 174.

Aluminium or copper conductors (aluminium armour, galvanised steel optional). Bare copper grounding conductor twisted with the cores. CSA C22.1:24 (standard, read 2026-11-10): Table 19 gives TECK90 90 C, in damp and wet locations, in raceways and as direct burial with its jacket, exposed to sunlight under Rule 2-136; Table D1: 600, 1000 and 5000 V, one conductor 6 AWG to 2000 kcmil or two or more 14 AWG to 2000 kcmil, cross-linked polyethylene or EPR, a thermoset or thermoplastic jacket and interlocking metal armour, with or without an overall covering.

Documents and pages the readings were taken from

CSA (Canada): how to read the cable type names

Not equivalent, because

IEC 60332-3-24 (cat. C) ≠ FT4 / IEEE 1202 ≠ UL 1685

Not equivalent, because The burner, the flame time and the char limit differ.

IEC 60332-3-24 (cat. C)

  • 1.5 litres of non-metallic material per metre on a vertical ladder, 20 min of flame. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
  • Pass: char height at most 2.5 m above the burner. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)

FT4 / IEEE 1202

UL 1685

All the comparisons →

TECK90 as the cable designer builds it, 3/C 2 AWG, 1000 V

Overall diameter 35.0 mm, about 1,760 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE1.510.2
Separation tapePolyester0.1022.3
Inner covering / beddingPVC2.026.3
Interlocked armourAluminium3.032.4
SheathPVC1.335.0

TECK90 on a drum

The smallest drum that passes every check, for 35 mm and about 1,760 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 50x32x23, wood NEMA reels (North America), American Wire Group9 of 9984 kg
1,000 mNEMA 68x38x28, wood NEMA reels (North America), American Wire Group12 of 142,010 kg

Barrel at least 15 × OD = 524 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: TECK90

TECK90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with TECK90

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More CSA (Canada) designations

TECK90