TECK90
TECK90 is a CSA (Canada) cable designation: TECK = Armoured cable with inner and outer PVC jackets (trade name of the type); 90 = Maximum conductor temperature 90 C; TECK90 = Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 174.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: CSA C22.2 No. 131: Type TECK 90 cable. How the values are sourced
Worked reading of TECK90 3/C 2 AWG, 1000 V:
TECK90: TECK = Armoured cable with inner and outer PVC jackets (trade name of the type); 90 = Maximum conductor temperature 90 C; TECK90 = Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 1743/C 2 AWG, 1000 V: 3 cores, each copper 2 AWG (33.6 mm²); rated voltage 1000 V
CSA (Canada)
| Symbol | Meaning |
|---|---|
TECK | Armoured cable with inner and outer PVC jackets (trade name of the type) |
90 | Maximum conductor temperature 90 C |
TECK90 | Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. 600 V, 1000 V or 5 kV, 90 C, FT4. CSA C22.2 No. 131 and No. 174 |
What is TECK90 cable?
TECK90: Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering. Rating: 600 V, 1000 V or 5 kV, 90 C, FT4. Standard: CSA C22.2 No. 131 and No. 174.
Aluminium or copper conductors (aluminium armour, galvanised steel optional). Bare copper grounding conductor twisted with the cores. CSA C22.1:24 (standard, read 2026-11-10): Table 19 gives TECK90 90 C, in damp and wet locations, in raceways and as direct burial with its jacket, exposed to sunlight under Rule 2-136; Table D1: 600, 1000 and 5000 V, one conductor 6 AWG to 2000 kcmil or two or more 14 AWG to 2000 kcmil, cross-linked polyethylene or EPR, a thermoset or thermoplastic jacket and interlocking metal armour, with or without an overall covering.
Documents and pages the readings were taken from
- nassaunationalcable.com
- electricalindustry.ca
- gov.nl.ca
- nexans.ca
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-473) and Appendix D Table D1 (pp. 766-770), read 2026-11-10 (the Rules, Sections 0 to 86, not held)
Not equivalent, because
IEC 60332-3-24 (cat. C) ≠ FT4 / IEEE 1202 ≠ UL 1685
Not equivalent, because The burner, the flame time and the char limit differ.
IEC 60332-3-24 (cat. C)
- 1.5 litres of non-metallic material per metre on a vertical ladder, 20 min of flame. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
- Pass: char height at most 2.5 m above the burner. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
FT4 / IEEE 1202
- A 20 kW burner (70,000 Btu/h) for 20 min. Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
- Pass: char at most 1.5 m. Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
UL 1685
- Pass (UL exposure): char below 8 ft (2.44 m). Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
TECK90 as the cable designer builds it, 3/C 2 AWG, 1000 V
Overall diameter 35.0 mm, about 1,760 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 1.5 | 10.2 |
| Separation tape | Polyester | 0.10 | 22.3 |
| Inner covering / bedding | PVC | 2.0 | 26.3 |
| Interlocked armour | Aluminium | 3.0 | 32.4 |
| Sheath | PVC | 1.3 | 35.0 |
TECK90 on a drum
The smallest drum that passes every check, for 35 mm and about 1,760 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 50x32x23, wood NEMA reels (North America), American Wire Group | 9 of 9 | 984 kg |
| 1,000 m | NEMA 68x38x28, wood NEMA reels (North America), American Wire Group | 12 of 14 | 2,010 kg |
Barrel at least 15 × OD = 524 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: TECK90
TECK90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²