RW90
RW90 is a CSA (Canada) cable designation: R = Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV; W = Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry; 90 = Maximum conductor temperature 90 C; RW90 = Crosslinked polyethylene insulated building wire, 90 C, wet locations. 600 V, 90 C wet or dry. CSA C22.2 No. 38.
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of RW90 12 AWG, 600 V:
RW90: R = Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV; W = Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry; 90 = Maximum conductor temperature 90 C; RW90 = Crosslinked polyethylene insulated building wire, 90 C, wet locations. 600 V, 90 C wet or dry. CSA C22.2 No. 3812 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V
CSA (Canada)
| Symbol | Meaning |
|---|---|
R | Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV |
W | Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry |
90 | Maximum conductor temperature 90 C |
RW90 | Crosslinked polyethylene insulated building wire, 90 C, wet locations. 600 V, 90 C wet or dry. CSA C22.2 No. 38 |
What is RW90 cable?
RW90: Crosslinked polyethylene insulated building wire, 90 C, wet locations. Rating: 600 V, 90 C wet or dry. Standard: CSA C22.2 No. 38.
Often printed "RW90 OR RHW-2 2KV OR RWU90 1KV": one wire with several listings. The 2 kV belongs to the UL RHW-2 listing. Copper or aluminium. CSA C22.1:24 (standard, read 2026-11-10): Table 19 gives RW90 90 C in dry, damp and wet locations, in raceways, in cable trays under Rule 12-2202 5), exposed to sunlight under Rule 2-136, not for direct burial; Table D1: 600, 1000 and 2000 V, one conductor, 14 AWG to 2000 kcmil, cross-linked polyethylene, no covering or a thermoplastic or thermoset one.
Documents and pages the readings were taken from
- southwire.com
- kristechwire.com
- sycor.com
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-473) and Appendix D Table D1 (pp. 766-770), read 2026-11-10 (the Rules, Sections 0 to 86, not held)
- UL 44 ed. 19 / CSA C22.2 No. 38-18 / NMX-J-451-ANCE-2018: Thermoset-Insulated Wires and Cables, Table 1 and Annex A, read 2026-11-08
Fire behaviour (EU CPR)
PE sheath (RW90).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
RW90: equivalents in other countries
Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | no letters for this build | Close | Insulation 0.76 → 0.7 mm; Overall diameter 3.79 → 3.67 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
RW90 as the cable designer builds it, 12 AWG, 600 V
Overall diameter 3.8 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.76 | 3.8 |
RW90 on a drum
The smallest drum that passes every check, for 3.8 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 14x10x5, wood NEMA reels (North America), Okonite | 15 of 18 | 22 kg |
| 1,000 m | NEMA 18x10x6, wood NEMA reels (North America), Okonite | 23 of 29 | 45 kg |
Barrel at least 20 × OD = 76 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: RW90
RW90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with RW90
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.