CSA (Canada)

Canada · 21 types · CSA (Canada): how to read the cable type names

RW90Crosslinked polyethylene insulated building wire, 90 C, wet locations (600 V, 90 C wet or dry)
RWU90RW90 construction rated 1000 V, approved for direct burial (1000 V, 90 C wet or dry)
RWA90Aluminium (8000-series ACM) building wire, XLPE, 90 C (600 V, 90 C)
RW75Crosslinked polyethylene building wire, 75 C (600 V, 75 C wet or dry)
TW75PVC building wire, 75 C, older construction replaced by T90 (600 V, 75 C)
TWUPVC building wire and direct burial cable, wet or dry: TWU 60 C, TWU75 75 C (legend TYPE TWU CABLE 75C 600V TW) (600 V; TWU 60 C, TWU75 75 C, wet or dry)
TWHThermoplastic 600 V wire used as an insulated ground conductor (UNVERIFIED) (600 V)
T90 NYLONThin-wall PVC building wire with nylon covering: 90 C dry, 75 C wet (600 V, 90 C dry, 75 C wet, 60 C oil)
NMD90Non-metallic sheathed cable for dry locations, 300 V, 90 C (300 V, 90 C, FT1)
NMWUNon-metallic sheathed cable for wet and underground use, 300 V (300 V, 60 C conductor limit)
AC90Armoured cable: copper conductors in interlocking aluminium armour, no overall jacket, dry locations (600 V, 90 C)
ACG90Armoured cable, G version of AC90: two or more conductors, 14 to 6 AWG, dry locations (600 V, 90 C)
ACWU90Armoured cable with an overall PVC jacket: dry and wet, direct burial, FT4 (600 V, 90 C, FT4, -40 C)
TECK90Armoured power cable: XLPE conductors, PVC inner jacket, interlocking aluminium armour, PVC overall covering (600 V, 1000 V or 5 kV, 90 C, FT4)
RA90Aluminium-sheathed (MC-HL type) cable, XLPE (600 V or 1000 V, 90 C)
RC90Copper-sheathed cable, silicone insulated (600 V or 1000 V, 90 C)
RW90-TCRW90 with a tray cable listing (1/0 and larger on the DLO page) (600 V, 90 C)
RPVU90Canadian photovoltaic cable: thermoset insulation, sunlight resistant, direct burial, 90 C wet, 105 C dry (600 / 1000 / 2000 V)
CICControl and instrumentation cable, unarmoured: XLPE or PVC cores in pairs or triads, screens, FR PVC jacket (300 V (also 600 V, 1000 V))
ACICControl and instrumentation cable, armoured: as CIC with an aluminium interlocking armour and an overall jacket (300 V (also 600 V, 1000 V))
TEWTEW: equipment and lead wire (a Canadian Electrical Code type): one copper conductor, PVC insulation (600 V; -30 to 105 C dry, 60 C exposed to water or oil; flame FT-1 (CSA) and VW-1 (UL))

Cable designations read in this system