NMD90
NMD90 is a CSA (Canada) cable designation: NM = Non-metallic sheathed cable; D = Dry (and damp) locations: CSA C22.1:24 Table 19 (p. 470) allows NMD90 in dry and damp locations, not wet; 90 = Maximum conductor temperature 90 C; NMD90 = Non-metallic sheathed cable for dry locations, 300 V, 90 C. 300 V, 90 C, FT1. CSA C22.2 No. 48.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: CSA C22.2 No. 48: Nonmetallic sheathed cable. How the values are sourced
Worked reading of NMD90 2/C 14 AWG, 300 V:
NMD90: NM = Non-metallic sheathed cable; D = Dry (and damp) locations: CSA C22.1:24 Table 19 (p. 470) allows NMD90 in dry and damp locations, not wet; 90 = Maximum conductor temperature 90 C; NMD90 = Non-metallic sheathed cable for dry locations, 300 V, 90 C. 300 V, 90 C, FT1. CSA C22.2 No. 482/C 14 AWG, 300 V: 2 cores, each copper 14 AWG (2.1 mm²); rated voltage 300 V
Related cable types: NMD90 14/2 300 V
CSA (Canada)
| Symbol | Meaning |
|---|---|
NM | Non-metallic sheathed cable |
D | Dry (and damp) locations: CSA C22.1:24 Table 19 (p. 470) allows NMD90 in dry and damp locations, not wet |
90 | Maximum conductor temperature 90 C |
NMD90 | Non-metallic sheathed cable for dry locations, 300 V, 90 C. 300 V, 90 C, FT1. CSA C22.2 No. 48 |
What is NMD90 cable?
NMD90: Non-metallic sheathed cable for dry locations, 300 V, 90 C. Rating: 300 V, 90 C, FT1. Standard: CSA C22.2 No. 48.
The Nassau page calls the insulation both "90C XLPE (R90)" and "white PVC Nylon T90"; drawn as PVC with nylon (sources disagree). Loomex and Canadex are trade names (Guillevin article, Nexans line card). CSA C22.1:24 (standard, read 2026-11-10): Table D1 allows both insulations the sources name: 90 C heat-resistant thermoplastic with a nylon sheath, or cross-linked polyethylene with no covering, under a thermoplastic outer covering; 300 V, 2, 3 or 4 conductors, 14 to 2 AWG. Table 19: 90 C, dry and damp locations, not wet; feeders, branch circuits and Class 2 circuits, not consumer's services; exposed or concealed, in raceways under Rule 12-568 2), not in cable trays, not for direct burial, not exposed to sunlight.
Documents and pages the readings were taken from
- nassaunationalcable.com
- electricalindustry.ca
- nexans.ca
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-473) and Appendix D Table D1 (pp. 766-770), read 2026-11-10 (the Rules, Sections 0 to 86, not held)
Not equivalent, because
IEC 60332-1-2 ≠ VW-1 (UL 2556 FV-2) / FT1
Not equivalent, because The flame, the number of flame applications and the pass criterion differ: a cable that passes one has not shown that it passes the other.
IEC 60332-1-2
- One 1 kW flame on a single vertical cable, applied once for a time set by the cable diameter. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- Pass: the char ends at least 50 mm below the top clamp and no lower than 540 mm below it. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- CPR class Eca uses the same test: the flame stops within 425 mm. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)
VW-1 (UL 2556 FV-2) / FT1
- 5 flame applications of 15 s each. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
- Judged by a paper indicator flag above the flame and cotton below the cable; their limits are not held here. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
NMD90 as the cable designer builds it, 2/C 14 AWG, 300 V
Flat, 9.9 × 4.9 mm (width × thickness), about 110 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.76 | 3.1 |
| Nylon jacket (polyamide) | Nylon (PA) | 0.10 | 3.4 |
| Sheath | PVC | 0.76 | 4.9 |
NMD90 on a drum
The smallest drum that passes every check, for 9.9 mm and about 110 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 24x18x10, wood NEMA reels (North America), American Wire Group, Okonite | 11 of 14 | 66–69 kg |
| 1,000 m | NEMA 30x18x12, wood NEMA reels (North America), American Wire Group, Okonite | 17 of 19 | 128–130 kg |
Barrel at least 15 × OD = 148 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NMD90
NMD90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²