RW75
RW75 is a CSA (Canada) cable designation: R = Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV; W = Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry; 75 = Maximum conductor temperature 75 C; RW75 = Crosslinked polyethylene building wire, 75 C. 600 V, 75 C wet or dry. CSA C22.2 No. 38.
2 coding systems recognise this code
Standard, worked reading and related types
Worked reading of RW75:
RW75: R = Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV; W = Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry; 75 = Maximum conductor temperature 75 C; RW75 = Crosslinked polyethylene building wire, 75 C. 600 V, 75 C wet or dry. CSA C22.2 No. 38
Related cable types: TW75
CSA (Canada)
| Symbol | Meaning |
|---|---|
R | Thermoset (crosslinked) insulation: CSA C22.1:24 Table 19 (p. 469) groups R90, RW75, RW90, RWU75 and RWU90 as thermoset insulated conductors; Table D1 (p. 767) gives cross-linked polyethylene, EPR or EPCV |
W | Suitable for wet locations: CSA C22.1:24 Table 19 (p. 469) allows RW75, RW90 and RWU90 in wet locations and R90 (no W) in dry and damp ones only; UL 44 / CSA C22.2 No. 38-18 Table 1: RW90 90 C wet or dry, R90 90 C dry |
75 | Maximum conductor temperature 75 C |
RW75 | Crosslinked polyethylene building wire, 75 C. 600 V, 75 C wet or dry. CSA C22.2 No. 38 |
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
R | Flexible Cable |
W | Oil And Open Weather Resistant |
7 | Non-Magnetic Metal Wire Armour |
5 | Cross-Linked Polyolefin Outer Sheath |
How to read a China (GB / JB/T / MT cable model codes) cable code
What is RW75 cable?
RW75: Crosslinked polyethylene building wire, 75 C. Rating: 600 V, 75 C wet or dry. Standard: CSA C22.2 No. 38.
CSA C22.1:24 (standard, read 2026-11-11): Table 19 (p. 469) gives RW75 75 C in dry, damp and wet locations, in raceways and cable trays, not as direct burial; Table D1 (p. 767): CSA C22.2 No. 38, 600, 1000 and 2000 V (5000 V from 8 AWG), cross-linked polyethylene, EPR or EPCV. UL 44 / CSA C22.2 No. 38-18 Table 1: 75 C wet or dry, 600, 1000, 2000 or 5000 V.
Documents and pages the readings were taken from
- sycor.com
- UL 44 ed. 19 / CSA C22.2 No. 38-18 / NMX-J-451-ANCE-2018: Thermoset-Insulated Wires and Cables, Table 1 and Annex A, read 2026-11-08
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-474) and Appendix D Table D1 (pp. 766-773), read 2026-11-11 (the Rules, Sections 0 to 86, not held)
Fire behaviour (EU CPR)
PE sheath (RW75).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Laying, sizes and datasheet: RW75
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Work with RW75
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.