AC90
AC90 is a CSA (Canada) cable designation: AC = Armoured cable, interlocking armour; 90 = Maximum conductor temperature 90 C; AC90 = Armoured cable: copper conductors in interlocking aluminium armour, no overall jacket, dry locations. 600 V, 90 C. CSA C22.2 No. 51.
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of AC90 2/C 14 AWG, 600 V:
AC90: AC = Armoured cable, interlocking armour; 90 = Maximum conductor temperature 90 C; AC90 = Armoured cable: copper conductors in interlocking aluminium armour, no overall jacket, dry locations. 600 V, 90 C. CSA C22.2 No. 512/C 14 AWG, 600 V: 2 cores, each copper 14 AWG (2.1 mm²); rated voltage 600 V
CSA (Canada)
| Symbol | Meaning |
|---|---|
AC | Armoured cable, interlocking armour |
90 | Maximum conductor temperature 90 C |
AC90 | Armoured cable: copper conductors in interlocking aluminium armour, no overall jacket, dry locations. 600 V, 90 C. CSA C22.2 No. 51 |
What is AC90 cable?
AC90: Armoured cable: copper conductors in interlocking aluminium armour, no overall jacket, dry locations. Rating: 600 V, 90 C. Standard: CSA C22.2 No. 51.
Insulation drawn as XLPE per the NL specification; paper wrap and a bonding conductor as on ACWU90. CSA C22.1:24 (standard, read 2026-11-10): Table 19 gives AC90 90 C in dry locations only (damp and wet: no), not in raceways, not for direct burial; Table D1: 600, 1000 and 2000 V, one or more conductors, 14 AWG to 2000 kcmil, cross-linked polyethylene, interlocking metal armour.
Documents and pages the readings were taken from
- electricalindustry.ca
- gov.nl.ca
- nexans.ca
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-473) and Appendix D Table D1 (pp. 766-770), read 2026-11-10 (the Rules, Sections 0 to 86, not held)
AC90 as the cable designer builds it, 2/C 14 AWG, 600 V
Overall diameter 11.5 mm, about 120 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.76 | 3.1 |
| Separation tape | Paper | 0.10 | 6.5 |
| Interlocked armour | Aluminium | 2.5 | 11.5 |
AC90 on a drum
The smallest drum that passes every check, for 11.5 mm and about 120 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 24x18x10, wood NEMA reels (North America), American Wire Group, Okonite | 12 of 12 | 71–74 kg |
| 1,000 m | NEMA 32x24x14, wood NEMA reels (North America), American Wire Group, Okonite | 13 of 16 | 145–150 kg |
Barrel at least 15 × OD = 172 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AC90
AC90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with AC90
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.