TEW
TEW is a CSA (Canada) cable designation: TEW = Equipment and lead wire, PVC insulation, 600 V, 105 C dry, 60 C wet or oil (CSA C22.2 No. 127); TEW = TEW: equipment and lead wire (a Canadian Electrical Code type): one copper conductor, PVC insulation. 600 V; -30 to 105 C dry, 60 C exposed to water or oil; flame FT-1 (CSA) and VW-1 (UL). CSA C22.2 No. 127 (equipment and lead wires); a Canadian wire type in UL 758:2014 cl. 52.1(b).
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of TEW:
TEW: TEW = Equipment and lead wire, PVC insulation, 600 V, 105 C dry, 60 C wet or oil (CSA C22.2 No. 127); TEW = TEW: equipment and lead wire (a Canadian Electrical Code type): one copper conductor, PVC insulation. 600 V; -30 to 105 C dry, 60 C exposed to water or oil; flame FT-1 (CSA) and VW-1 (UL). CSA C22.2 No. 127 (equipment and lead wires); a Canadian wire type in UL 758:2014 cl. 52.1(b)
CSA (Canada)
| Symbol | Meaning |
|---|---|
TEW | Equipment and lead wire, PVC insulation, 600 V, 105 C dry, 60 C wet or oil (CSA C22.2 No. 127) |
TEW | TEW: equipment and lead wire (a Canadian Electrical Code type): one copper conductor, PVC insulation. 600 V; -30 to 105 C dry, 60 C exposed to water or oil; flame FT-1 (CSA) and VW-1 (UL). CSA C22.2 No. 127 (equipment and lead wires); a Canadian wire type in UL 758:2014 cl. 52.1(b) |
What is TEW cable?
TEW: equipment and lead wire (a Canadian Electrical Code type): one copper conductor, PVC insulation. Rating: 600 V; -30 to 105 C dry, 60 C exposed to water or oil; flame FT-1 (CSA) and VW-1 (UL). Standard: CSA C22.2 No. 127 (equipment and lead wires); a Canadian wire type in UL 758:2014 cl. 52.1(b).
UL 758 Third Edition (May 2, 2014, revisions through December 8, 2014), cl. 52.1(b), p. 85 (standard, read 2026-10-31): an appliance wiring material may also comply with one or more Canadian wire types for Canadian Electrical Code (CEC) types, its example "Type TEW equipment wire"; the extra type is then marked on the surface and the tag (cl. 52.2). TEW per CSA C22.2 No. 127 (equipment and lead wires): one copper conductor, PVC insulation, 600 V, -30 to 105 C dry, 60 C when exposed to water or oil, flame FT-1 (the CSA test) and VW-1 (the UL test); the same wire is commonly also listed as UL AWM styles 1015, 1028, 1283 and 1284. CSA C22.2 No. 127 itself is not held.
Documents and pages the readings were taken from
- UL 758, Third Edition, May 2, 2014, revisions through December 8, 2014: cl. 52.1(b), p. 85
- cdn.gescan.com
- cdn.gescan.com
- sycor.com
Fire behaviour (EU CPR)
PVC sheath (TEW).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Not equivalent, because
IEC 60332-1-2 ≠ VW-1 (UL 2556 FV-2) / FT1
Not equivalent, because The flame, the number of flame applications and the pass criterion differ: a cable that passes one has not shown that it passes the other.
IEC 60332-1-2
- One 1 kW flame on a single vertical cable, applied once for a time set by the cable diameter. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- Pass: the char ends at least 50 mm below the top clamp and no lower than 540 mm below it. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- CPR class Eca uses the same test: the flame stops within 425 mm. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)
VW-1 (UL 2556 FV-2) / FT1
- 5 flame applications of 15 s each. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
- Judged by a paper indicator flag above the flame and cotton below the cable; their limits are not held here. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
Laying, sizes and datasheet: TEW
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Work with TEW