ACWU90
ACWU90 is a CSA (Canada) cable designation: AC = Armoured cable, interlocking armour; W = Wet locations: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 in wet locations, AC90 in dry ones only; U = Underground / direct burial: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 as direct burial, AC90 not; 90 = Maximum conductor temperature 90 C; ACWU90 = Armoured cable with an overall PVC jacket: dry and wet, direct burial, FT4. 600 V, 90 C, FT4, -40 C. CSA C22.2 No. 51 and No. 174.
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of ACWU90 2/C 14 AWG, 600 V:
ACWU90: AC = Armoured cable, interlocking armour; W = Wet locations: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 in wet locations, AC90 in dry ones only; U = Underground / direct burial: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 as direct burial, AC90 not; 90 = Maximum conductor temperature 90 C; ACWU90 = Armoured cable with an overall PVC jacket: dry and wet, direct burial, FT4. 600 V, 90 C, FT4, -40 C. CSA C22.2 No. 51 and No. 1742/C 14 AWG, 600 V: 2 cores, each copper 14 AWG (2.1 mm²); rated voltage 600 V
CSA (Canada)
| Symbol | Meaning |
|---|---|
AC | Armoured cable, interlocking armour |
W | Wet locations: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 in wet locations, AC90 in dry ones only |
U | Underground / direct burial: CSA C22.1:24 Table 19 (p. 473) allows ACWU90 as direct burial, AC90 not |
90 | Maximum conductor temperature 90 C |
ACWU90 | Armoured cable with an overall PVC jacket: dry and wet, direct burial, FT4. 600 V, 90 C, FT4, -40 C. CSA C22.2 No. 51 and No. 174 |
What is ACWU90 cable?
ACWU90: Armoured cable with an overall PVC jacket: dry and wet, direct burial, FT4. Rating: 600 V, 90 C, FT4, -40 C. Standard: CSA C22.2 No. 51 and No. 174.
Aluminium ACM conductors, XLPE (RW90), bare aluminium bonding wire, kraft paper binder, aluminium interlocked armour, black PVC jacket. Copper also made. CSA C22.1:24 (standard, read 2026-11-10): Table 19 gives ACWU90 90 C in dry, damp and wet locations, in raceways, as direct burial, exposed to sunlight under Rule 2-136; Table D1: 600, 1000 and 2000 V, one or more conductors, 14 AWG to 2000 kcmil, cross-linked polyethylene, interlocking metal armour and a flame-tested thermoplastic jacket.
Documents and pages the readings were taken from
- southwire.com
- nassaunationalcable.com
- gov.nl.ca
- CSA C22.1:24: Canadian Electrical Code, Part I (March 2024), Table 19 (pp. 469-473) and Appendix D Table D1 (pp. 766-770), read 2026-11-10 (the Rules, Sections 0 to 86, not held)
Not equivalent, because
IEC 60332-3-24 (cat. C) ≠ FT4 / IEEE 1202 ≠ UL 1685
Not equivalent, because The burner, the flame time and the char limit differ.
IEC 60332-3-24 (cat. C)
- 1.5 litres of non-metallic material per metre on a vertical ladder, 20 min of flame. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
- Pass: char height at most 2.5 m above the burner. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
FT4 / IEEE 1202
- A 20 kW burner (70,000 Btu/h) for 20 min. Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
- Pass: char at most 1.5 m. Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
UL 1685
- Pass (UL exposure): char below 8 ft (2.44 m). Sources: M. Hirschler, FAA Fire and Materials conference 2001, slides (quoted by others); VTEC Laboratories, cable fire tests (quoted by others)
ACWU90 as the cable designer builds it, 2/C 14 AWG, 600 V
Overall diameter 14.5 mm, about 210 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.76 | 3.1 |
| Separation tape | Paper | 0.10 | 6.5 |
| Interlocked armour | Aluminium | 2.5 | 11.5 |
| Sheath | PVC | 1.5 | 14.5 |
ACWU90 on a drum
The smallest drum that passes every check, for 14.5 mm and about 210 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 30x18x12, wood NEMA reels (North America), American Wire Group, Okonite | 12 of 13 | 123–125 kg |
| 1,000 m | NEMA 36x24x17, wood NEMA reels (North America), American Wire Group, Okonite | 14 of 14 | 241–247 kg |
Barrel at least 15 × OD = 218 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: ACWU90
ACWU90 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Terms on this page: direct burial
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro