Cable tests that are not equivalent, and why

IEC 60332-3-24 (cat. C) ≠ FT4 / IEEE 1202 ≠ UL 1685

Not equivalent, because The burner, the flame time and the char limit differ.

IEC 60332-3-24 (cat. C)

  • 1.5 litres of non-metallic material per metre on a vertical ladder, 20 min of flame. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)
  • Pass: char height at most 2.5 m above the burner. Sources: IEC 60332-3-24:2000+A1:2008 (edition 1.1, 2009-02), Table A.1 p. 12; cl 5.1 p. 7; cl 5.3 pp. 8-9; Annex A p. 12; Annex B p. 13 (informative); cl 7 (read in the standard)

FT4 / IEEE 1202

UL 1685

Values as the sources print them, every one with its source and how it was seen; where a value is not held, it says so. The cable's own standard and the specification decide which test applies.

Questions and answers

Is FT4 / IEEE 1202, UL 1685 equivalent to IEC 60332-3-24 (cat. C)?

No. The burner, the flame time and the char limit differ.