YAKXSFOY

YAKXSFOY est une désignation de câble PN (Poland) : Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; Fo = Round steel wire armour; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YAKXSFOY = YAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.

1 système de codification reconnaît cette désignation

PN (Poland)

SymboleSignification
YPVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names
AAluminium conductor (no letter: copper)
Kkabel: power cable family (not a copper letter)
XSCross-linked polyethylene (XLPE) insulation, replaces the final Y
FoRound steel wire armour
yPVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC)
YAKXSFOYYAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1

Comportement au feu (RPC européen)

  • Non propagateur de la flamme (y). L'essai sur câble unique qui fonde la classe Eca est l'EN 60332-1-2 (la flamme s'arrête en moins de 425 mm). Les câbles en faisceau sont essayés selon l'IEC 60332-3-24 catégorie C (1,5 l/m, 20 min, carbonisation d'au plus 2,5 m) ; ce n'est pas un essai de classe RPC, l'essai sur échelle du RPC pour B1ca à Dca est l'EN 50399.

Une classe RPC est déclarée par le fabricant dans sa déclaration des performances et imprimée sur la gaine (EN 50575 art. 7). Ce décodeur n'en attribue aucune. Ce que signifient les classes RPC →

Sources : projet d'EN 13501-6 et projet final FprEN 50575:2014 (projets, et non les textes publiés) ; IEC 60332-3-24:2000+A1:2008 ; projet d'EN 13501-3 A2.

Câbles apparentés