YAKXSFOY

YAKXSFOY ist ein Kabelkurzzeichen nach PN (Poland): Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; Fo = Round steel wire armour; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YAKXSFOY = YAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.

1 Kodiersystem erkennt dieses Kurzzeichen

PN (Poland)

SymbolBedeutung
YPVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names
AAluminium conductor (no letter: copper)
Kkabel: power cable family (not a copper letter)
XSCross-linked polyethylene (XLPE) insulation, replaces the final Y
FoRound steel wire armour
yPVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC)
YAKXSFOYYAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1

Brandverhalten (EU-Bauproduktenverordnung, CPR)

  • Flammwidrig (y). Die Einzelkabelprüfung hinter der Klasse Eca ist EN 60332-1-2 (die Flamme erlischt innerhalb von 425 mm). Gebündelte Kabel werden nach IEC 60332-3-24 Kategorie C geprüft (1,5 l/m, 20 min, Verkohlung höchstens 2,5 m); das ist keine Prüfung für eine CPR-Klasse, die CPR-Leiterprüfung für B1ca bis Dca ist EN 50399.

Eine CPR-Klasse erklärt der Hersteller in seiner Leistungserklärung und druckt sie auf den Mantel (EN 50575 Abschn. 7). Dieser Decoder weist keine Klasse zu. Was die CPR-Klassen bedeuten →

Quellen: Entwurf EN 13501-6 und Schlussentwurf FprEN 50575:2014 (Entwürfe, nicht die veröffentlichten Texte); IEC 60332-3-24:2000+A1:2008; Entwurf EN 13501-3 A2.

Verwandte Kabel