YAKXSFOY
YAKXSFOY to oznaczenie kabla wg PN (Poland): Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; Fo = Round steel wire armour; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YAKXSFOY = YAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
1 system kodowania rozpoznaje to oznaczenie
PN (Poland)
| Symbol | Znaczenie |
|---|---|
Y | PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names |
A | Aluminium conductor (no letter: copper) |
K | kabel: power cable family (not a copper letter) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
Fo | Round steel wire armour |
y | PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC) |
YAKXSFOY | YAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
Zachowanie w pożarze (rozporządzenie UE w sprawie wyrobów budowlanych, CPR)
Nierozprzestrzeniający płomienia (y). Badanie pojedynczego kabla, na którym opiera się klasa Eca, to EN 60332-1-2 (płomień gaśnie w granicach 425 mm). Kable w wiązce bada się według IEC 60332-3-24, kategoria C (1,5 l/m, 20 min, zwęglenie najwyżej 2,5 m); nie jest to badanie klasy CPR, a badanie drabinowe CPR dla B1ca do Dca to EN 50399.
Klasę CPR deklaruje producent w deklaracji właściwości użytkowych i nadrukowuje ją na powłoce (EN 50575, pkt 7). Ten dekoder nie przypisuje żadnej klasy. Co oznaczają klasy CPR →
Źródła: projekt EN 13501-6 i projekt końcowy FprEN 50575:2014 (projekty, nie teksty opublikowane); IEC 60332-3-24:2000+A1:2008; projekt EN 13501-3 A2.