Project requirements · Fire

Toxicity of fire gases

The combustion gases of the cable materials are below a toxicity index.

Open in the designer with this requirement

Constructions that meet it

  • Low-toxicity halogen-free compounds: changes no layer: a property of the sheath compound. Low-toxicity halogen-free compounds (no PVC, no fluoropolymers) (LSZH / EN 50306 S1, S2 sheaths). Drawbacks: Compound property.

Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro

Tests

  • EN 50305 clause 9.2 (rail): toxicity index ITC at 800 °C (CO, CO2, NOx, HCN, SO2 ...). Pass: EN 45545-2 R15/R16: ITC ≤ 10 (HL1), ≤ 10 (HL2), ≤ 6 (HL3)
  • NES 713 / Def Stan 02-713 (UK defence, marine): toxicity index of small specimens. Pass: set by the specification (value not found)
  • NF X70-100 (France): toxicity analysis. Pass: not found

How specifications state it

Rare outside rail, defence and marine; named by test and index limit.

Where it is asked for

  • rolling stock
  • naval ships
  • metro and tunnels