Low smoke (IEC 61034)

Burning cable gives little smoke, so people can see escape routes.

Open in the designer with this requirement

Constructions that meet it

  • Halogen-free low-smoke compounds: changes no layer: a property of the sheath compound. Halogen-free low-smoke compounds for sheath, bedding, fillers (and insulation) (LSZH / SHF1 / SHF2). Drawbacks: Every non-metallic layer contributes.

Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro

Tests

  • IEC 61034-1 / -2 (3 m cube): light transmittance during burning. Pass: minimum 60 % light transmittance (Draka datasheet); EN 45545-2 R15: HL1 ≥ 25 %, HL2 ≥ 50 %, HL3 ≥ 70 %; R16: HL2 ≥ 25 %, HL3 ≥ 50 %

How specifications state it

'Low smoke acc. to IEC 61034-2, light transmittance ≥ 60 %' (the limit comes from the referencing specification).

Where it is asked for

  • public buildings
  • tunnels and metro
  • ships and offshore
  • rolling stock
  • data centres