How to read a cable code: guides per coding system · PN (Poland) · Poland

PN (Poland): how to read the cable type names

Each name in PN (Poland) stands for a whole cable type: LYC, for example, comes with its own construction, standard and rating. The decoder knows 42 types of this system. Below: how the names are built, every type with its rating, and the sources the table names.

How a name is built

The type table splits each name into parts and records what each part means. A few names taken apart:

LYC

LStranded copper conductor, class 2
YcHeat-resistant PVC (90 C) insulation

LYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R)

LY

LStranded (multi-wire) copper conductor, class 2
YPVC insulation

LY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R)

YKY

YPVC sheath; the sheath letter comes first in Polish names
Kkabel: power cable family (not a copper letter)
YPVC insulation

YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J)

YAKY

YPVC sheath; the sheath letter comes first in Polish names
AAluminium conductor (no letter: copper)
Kkabel: power cable family (not a copper letter)
YPVC insulation

YAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J)

Every part used in the names

PartMeaningUsed in
YPVC insulationYKY YAKY XAKY YKYY YAKYY YNKY YKYFTY YKYFOY YKYEKTMY YAKYFTY YKSYFTY YDY YDYP YDYT YLY ADY DY LY LGY YKSY YKSLY YSTY YTDY
Kkabel: power cable family (not a copper letter)YKY YAKY YKXS YAKXS XAKXS XAKY YKYY YAKYY YAKYXS YNKY YKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY
AAluminium conductor (no letter: copper)YAKY YAKXS XAKXS XAKY YAKYY YAKYXS YAKYFTY YAKXSFOY
YPVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish namesYKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY YKSYFTY
yPVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC)YKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY YKSYFTY
YPVC sheath; the sheath letter comes first in Polish namesYKY YAKY YKXS YAKXS YKYY YAKYY YAKYXS
XSCross-linked polyethylene (XLPE) insulation, replaces the final YYKXS YAKXS XAKXS YAKYXS YKXSFTY YKXSEKTMY YAKXSFOY
YPVC sheathYDY YDYP YDYT YLY YKSY YSTY YTDY
FtGalvanised steel tape armour (Ftl: varnished tape)YKYFTY YKXSFTY YAKYFTY YKSYFTY
YPVC (insulation and sheath)OMY OMYP OWY OWYP
ULongitudinally sealed: water-blocking tapesXRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS
HH: radial field (HD 620 S3 10-R Table 5)XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS
Kkabel: power cable familyXRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS
XSCross-linked polyethylene (XLPE) insulationXRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS
1Type 1: normal insulation thicknessXRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS
yExtruded filler / inner covering between the cores (lower-case y right after K)YKYY YAKYY YAKYXS
KSSignalling / control cable family (K cable, S signalling)YKSYFTY YKSY YKSLY
DSolid copper conductor, class 1YDYP YDYT DYC
YcHeat-resistant PVC (90 C) insulationDYC LYC LGYC
RR: transversal (radial) water tightness, a metal foil bonded to the PE sheath (HD 620 S3 10-R Table 5, No. 9)XRUHAKXS XRUHKXS XnRUHAKXS
AAluminium working conductorXRUHAKXS XnRUHAKXS XnUHAKXS
Xpolyethylene (PE) sheath; the sheath letter comes first in Polish namesXAKXS XAKY
FoRound steel wire armourYKYFOY YAKXSFOY
ektmCopper tape screenYKYEKTMY YKXSEKTMY
LStranded (multi-wire) copper conductor, class 2YLY LY
LgFlexible stranded copper conductorLGY LGYC
OMO-type cord, household (oponowy mieszkaniowy)OMY OMYP
pFlat (plaski) versionOMYP OWYP
OWO-type cord, workshop (oponowy warsztatowy)OWY OWYP
XThermoplastic polyethylene sheathXRUHAKXS XRUHKXS
XnXn: flame retardant PE sheath (HD 620 S3 10-R Table 5)XnRUHAKXS XnUHAKXS
Ynself-extinguishing PVC sheath; the sheath letter comes first in Polish namesYNKY
DSolid (single-wire) conductor, class 1; copperYDY
pFlat (plaski) cross-section; the sheath is called "opona" (tyre)YDYP
tFlush-mounted, for plaster (wtynkowy)YDYT
AAluminium conductorADY
DSolid (single-wire) conductorADY
DSolid (single-wire) copper conductor, class 1DY
LStranded copper conductor, class 2LYC
YPVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing)YKSLY
LStranded copper conductorYKSLY
StControl wire (przewod sterowniczy)YSTY
TTelecommunication wire (przewod telekomunikacyjny)YTDY
DSolid copper conductor, 0,5 mmYTDY
XThermoplastic polyethylene sheath (powłoka z polietylenu termoplastycznego)XUHAKXS
UReturn conductor sealed longitudinally by water-blocking tapes (uszczelnioną wzdłużnie)XUHAKXS
HRadial electric field: semiconducting layers (o polu promieniowym)XUHAKXS
AAluminium working conductor (z żyłą roboczą aluminiową)XUHAKXS
KPower cable (kable elektroenergetyczne jednożyłowe)XUHAKXS
XSCross-linked polyethylene insulation (izolacji z polietylenu usieciowanego)XUHAKXS
1Normal insulation thickness (o normalnej grubości izolacji)XUHAKXS

What the type table says about the names

Quoted from the notes of the type table, with the types they belong to.

  • Polish names read outside-in: the sheath letter comes first, then the conductor metal (A = aluminium, none = copper), K, then the insulation. (YKY, YAKY, YKXS, YAKXS, XAKXS, XAKY +13)
  • Without the żo mark the cable has NO protective core (3x2,5 = brown, black, grey); with żo the count includes the green-yellow core. (YKY, YAKY, YKXS, YAKXS, XAKXS, XAKY +13)

Every type in PN (Poland)

TypeDescriptionRating
YKYYKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J)0,6/1 kV (3,6/6 kV also listed)
YAKYYAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J)0,6/1 kV
YKXSYKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C0,6/1 kV
YAKXSYAKXS: aluminium power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C (closest VDE: NA2XY-J / NA2XY-O)0,6/1 kV
XAKXSXAKXS: aluminium power cable, XLPE insulation and PE sheath, 0,6/1 kV, 90 C (closest VDE: NA2X2Y-J / NA2X2Y-O)0,6/1 kV
XAKYXAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O)0,6/1 kV
YKYYYKyY: copper power cable with an extruded filler between the cores, PVC insulation and PVC sheath, 0,6/1 kV0,6/1 kV
YAKYYYAKyY / YAKYy: aluminium power cable with an extruded filler, PVC insulation and PVC sheath, 0,6/1 kV (also listed at 3,6/6 kV)0,6/1 kV
YAKYXSYAKyXS: aluminium power cable with an extruded filler, XLPE insulation and PVC sheath, 0,6/1 kV0,6/1 kV
YNKYYnKY: copper power cable like YKY with a self-extinguishing PVC sheath (Yn), 0,6/1 kV0,6/1 kV
YKYFTYYKYFty: YKY with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV (yn / (n): fire-retardant oversheath, (l): varnished tape)0,6/1 kV
YKYFOYYKYFoy: YKY with round steel wire armour and a PVC oversheath, 0,6/1 kV ((n): fire-retardant oversheath)0,6/1 kV
YKYEKTMYYKYektmy: YKY with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV0,6/1 kV
YKXSFTYYKXSFty: YKXS (XLPE) with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV0,6/1 kV
YKXSEKTMYYKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV0,6/1 kV
YAKYFTYYAKYFty: YAKY (aluminium, PVC) with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV0,6/1 kV
YAKXSFOYYAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV0,6/1 kV
YKSYFTYYKSYFty: control / signalling cable YKSY with steel tape armour and a PVC oversheath, numbered cores, 0,6/1 kV0,6/1 kV
YDYYDY: round multicore installation wire, solid copper cores, PVC insulation and PVC sheath, 450/750 V450/750 V
YDYPYDYp: flat installation wire, solid copper cores, PVC insulation and flat PVC sheath, 300/500 V and 450/750 V300/500 V and 450/750 V
YDYTYDYt: flat installation wire for flush mounting (under plaster), solid copper cores, PVC, 300/500 V (also 450/750 V)300/500 V (also 450/750 V)
YLYYLY: round multicore wire, stranded copper cores (class 2), PVC insulation and PVC sheath, 0,6/1 kV0,6/1 kV
ADYADY: single-core wire with a solid aluminium conductor and PVC insulation, no sheathnot stated by the sources read (UNVERIFIED)
DYDY: single-core wire, solid copper conductor, PVC insulation, no sheath (= H05V-U / H07V-U)300/500 V and 450/750 V
LYLY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R)300/500 V and 450/750 V
LGYLgY: single-core wire, flexible stranded copper conductor, PVC insulation, no sheath (= H05V-K / H07V-K)300/500 V and 450/750 V
DYCDYc: single-core wire, solid copper, heat-resistant PVC (90 C) insulation (= H05V2-U / H07V2-U)300/500 V and 450/750 V
LYCLYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R)300/500 V and 450/750 V
LGYCLgYc: single-core wire, flexible copper, heat-resistant PVC (90 C) insulation (= H05V2-K / H07V2-K)300/500 V and 450/750 V
OMYOMY: round household cord, flexible copper, PVC / PVC, 300/300 V (= H03VV-F)300/300 V
OMYPOMYp: flat household cord, flexible copper, PVC / PVC, 300/300 V (= H03VVH2-F)300/300 V
OWYOWY: round workshop cord, flexible copper, PVC / PVC, 300/500 V (= H05VV-F)300/500 V
OWYPOWYp: flat workshop cord, flexible copper, PVC / PVC, 300/500 V (= H05VVH2-F)300/500 V
YKSYYKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J)0,6/1 kV
YKSLYYKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV300/500 V (also 0,6/1 kV)
YSTYYStY: control wire (przewod sterowniczy) with PVC insulation and PVC sheathnot stated by the sources read (UNVERIFIED)
YTDYYTDY: telecommunication wire, solid copper cores 0,5 mm, PVC insulation and PVC sheath, for alarm and intercom installationsup to 100 V (Eltrim page 124)
XRUHAKXSXRUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper screen, radially and longitudinally sealed, PE sheath, 6/10 to 18/30 kV6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1)
XRUHKXSXRUHKXS(1): single-core medium-voltage cable, copper conductor, XLPE insulation, copper screen, radially and longitudinally sealed, PE sheath, 6/10 to 18/30 kV6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1)
XnRUHAKXSXnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1)
XUHAKXSXUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen sealed longitudinally (water-blocking tapes), PE sheath, 6/10 to 18/30 kV (= NA2XS(F)2Y)6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1)
XnUHAKXSXnUHAKXS(1): XUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen sealed longitudinally, 6/10 to 18/30 kV6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1)

Marks written next to the name

Words and marks the decoder reads next to a type name of this system: each adds a property to whatever type it is written with.

MarkMeaningWritten as
żoIncludes a green-yellow protective core ("zyla ochronna"); without the mark the cable has no protective core. Typed ZO without the accent, or in parentheses, it means the sameŻO ZO
REConductor shape: round, solid, class 1RE
RMConductor shape: round, stranded, class 2RM
RMCConductor shape: round, stranded, compacted, class 2RMC
SMConductor shape: sector, stranded, class 2SM
SEConductor shape: sector, solid, class 1 (read by analogy; SE itself is not defined on a page read, UNVERIFIED)SE
ekwCommon screen on the coreEKW
ekwfCommon foil screen on the coreEKWF
ekoScreen of round wires (braid)EKO
ekpIndividually screened pairsEKP
ektTape screenEKT

Common questions

What is LYC cable?

LYC: LYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R). Rating: 300/500 V and 450/750 V. Standard: harmonised type (the PN standard number is not named by the sources read). The name reads: L (Stranded copper conductor, class 2) + Yc (Heat-resistant PVC (90 C) insulation).

What is LY cable?

LY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R). Rating: 300/500 V and 450/750 V. Standard: harmonised type (the PN standard number is not named by the sources read). The name reads: L (Stranded (multi-wire) copper conductor, class 2) + Y (PVC insulation).

What is the difference between YKY and YAKY?

YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J), 0,6/1 kV (3,6/6 kV also listed). YAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J), 0,6/1 kV. The names differ in: YAKY: A (Aluminium conductor (no letter: copper)).

PN (Poland): what does Y mean in a cable name?

Y has more than one meaning, depending on the type: PVC insulation (YKY, YAKY, XAKY, YKYY +19); PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names (YKYFTY, YKYFOY, YKYEKTMY, YKXSFTY +4); PVC sheath; the sheath letter comes first in Polish names (YKY, YAKY, YKXS, YAKXS +3); PVC sheath (YDY, YDYP, YDYT, YLY +3); PVC (insulation and sheath) (OMY, OMYP, OWY, OWYP); PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing) (YKSLY).

PN (Poland): what does żo mean next to a cable name?

żo: Includes a green-yellow protective core ("zyla ochronna"); without the mark the cable has no protective core. Typed ZO without the accent, or in parentheses, it means the same. Written as ŻO, ZO.

What is YKY cable?

YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J). Rating: 0,6/1 kV (3,6/6 kV also listed). Standard: PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue). The name reads: Y (PVC sheath; the sheath letter comes first in Polish names) + K (kabel: power cable family (not a copper letter)) + Y (PVC insulation).

Sources the type table names

Standards named in the table

  • PN-93/E-90400
  • PN-93/E-90401
  • PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue)
  • PN-HD 603 S1:2006/A3:2009
  • IEC 60502-1
  • PN-EN 50525-1
  • NF-EP-66:2012 (as printed in the Elpar catalogue)
  • NF-EP-12:2008 (as printed in the Elpar catalogue)
  • not stated by the sources read (letter key only)
  • harmonised type (the PN standard number is not named by the sources read)
  • PN-HD 21.5 S3:2004
  • PN-91/E-90103 (as printed by Eltrim)
  • PN-HD 21.5 S3:2004 family (as printed by Eltrim)
  • PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim)
  • Elpar ARCONTROL range (standard number not named by the pages read)
  • not stated by the sources read (listed in the Elpar key and product list)
  • ZN-ELT-2/2007 (Eltrim in-house)
  • HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27)
  • XLPE DIX 8 (1, p. 10-R-3). seen: standard
  • PN-HD 620 S3:2023-04 (makers)
  • HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Tables 8 and 10 (pp. 10-R-29, 10-R-30)
  • HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 7 (p. 10-R-28)
  • PN-HD 620-10C (older maker sheet)

Documents and pages the readings were taken from

Taken from the type table of this site, with the sources named above. Check the manufacturer's datasheet before you specify a cable.

Every type in PN (Poland) · Decode your own designation