How to read a cable code: guides per coding system · PN (Poland) · Poland
PN (Poland): how to read the cable type names
Each name in PN (Poland) stands for a whole cable type: LYC, for example, comes with its own construction, standard and rating. The decoder knows 42 types of this system. Below: how the names are built, every type with its rating, and the sources the table names.
How a name is built
The type table splits each name into parts and records what each part means. A few names taken apart:
LYC
| L | Stranded copper conductor, class 2 |
| Yc | Heat-resistant PVC (90 C) insulation |
LYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R)
LY
| L | Stranded (multi-wire) copper conductor, class 2 |
| Y | PVC insulation |
LY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R)
YKY
| Y | PVC sheath; the sheath letter comes first in Polish names |
| K | kabel: power cable family (not a copper letter) |
| Y | PVC insulation |
YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J)
YAKY
| Y | PVC sheath; the sheath letter comes first in Polish names |
| A | Aluminium conductor (no letter: copper) |
| K | kabel: power cable family (not a copper letter) |
| Y | PVC insulation |
YAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J)
Every part used in the names
| Part | Meaning | Used in |
|---|---|---|
| Y | PVC insulation | YKY YAKY XAKY YKYY YAKYY YNKY YKYFTY YKYFOY YKYEKTMY YAKYFTY YKSYFTY YDY YDYP YDYT YLY ADY DY LY LGY YKSY YKSLY YSTY YTDY |
| K | kabel: power cable family (not a copper letter) | YKY YAKY YKXS YAKXS XAKXS XAKY YKYY YAKYY YAKYXS YNKY YKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY |
| A | Aluminium conductor (no letter: copper) | YAKY YAKXS XAKXS XAKY YAKYY YAKYXS YAKYFTY YAKXSFOY |
| Y | PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names | YKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY YKSYFTY |
| y | PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC) | YKYFTY YKYFOY YKYEKTMY YKXSFTY YKXSEKTMY YAKYFTY YAKXSFOY YKSYFTY |
| Y | PVC sheath; the sheath letter comes first in Polish names | YKY YAKY YKXS YAKXS YKYY YAKYY YAKYXS |
| XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y | YKXS YAKXS XAKXS YAKYXS YKXSFTY YKXSEKTMY YAKXSFOY |
| Y | PVC sheath | YDY YDYP YDYT YLY YKSY YSTY YTDY |
| Ft | Galvanised steel tape armour (Ftl: varnished tape) | YKYFTY YKXSFTY YAKYFTY YKSYFTY |
| Y | PVC (insulation and sheath) | OMY OMYP OWY OWYP |
| U | Longitudinally sealed: water-blocking tapes | XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS |
| H | H: radial field (HD 620 S3 10-R Table 5) | XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS |
| K | kabel: power cable family | XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS |
| XS | Cross-linked polyethylene (XLPE) insulation | XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS |
| 1 | Type 1: normal insulation thickness | XRUHAKXS XRUHKXS XnRUHAKXS XnUHAKXS |
| y | Extruded filler / inner covering between the cores (lower-case y right after K) | YKYY YAKYY YAKYXS |
| KS | Signalling / control cable family (K cable, S signalling) | YKSYFTY YKSY YKSLY |
| D | Solid copper conductor, class 1 | YDYP YDYT DYC |
| Yc | Heat-resistant PVC (90 C) insulation | DYC LYC LGYC |
| R | R: transversal (radial) water tightness, a metal foil bonded to the PE sheath (HD 620 S3 10-R Table 5, No. 9) | XRUHAKXS XRUHKXS XnRUHAKXS |
| A | Aluminium working conductor | XRUHAKXS XnRUHAKXS XnUHAKXS |
| X | polyethylene (PE) sheath; the sheath letter comes first in Polish names | XAKXS XAKY |
| Fo | Round steel wire armour | YKYFOY YAKXSFOY |
| ektm | Copper tape screen | YKYEKTMY YKXSEKTMY |
| L | Stranded (multi-wire) copper conductor, class 2 | YLY LY |
| Lg | Flexible stranded copper conductor | LGY LGYC |
| OM | O-type cord, household (oponowy mieszkaniowy) | OMY OMYP |
| p | Flat (plaski) version | OMYP OWYP |
| OW | O-type cord, workshop (oponowy warsztatowy) | OWY OWYP |
| X | Thermoplastic polyethylene sheath | XRUHAKXS XRUHKXS |
| Xn | Xn: flame retardant PE sheath (HD 620 S3 10-R Table 5) | XnRUHAKXS XnUHAKXS |
| Yn | self-extinguishing PVC sheath; the sheath letter comes first in Polish names | YNKY |
| D | Solid (single-wire) conductor, class 1; copper | YDY |
| p | Flat (plaski) cross-section; the sheath is called "opona" (tyre) | YDYP |
| t | Flush-mounted, for plaster (wtynkowy) | YDYT |
| A | Aluminium conductor | ADY |
| D | Solid (single-wire) conductor | ADY |
| D | Solid (single-wire) copper conductor, class 1 | DY |
| L | Stranded copper conductor, class 2 | LYC |
| Y | PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing) | YKSLY |
| L | Stranded copper conductor | YKSLY |
| St | Control wire (przewod sterowniczy) | YSTY |
| T | Telecommunication wire (przewod telekomunikacyjny) | YTDY |
| D | Solid copper conductor, 0,5 mm | YTDY |
| X | Thermoplastic polyethylene sheath (powłoka z polietylenu termoplastycznego) | XUHAKXS |
| U | Return conductor sealed longitudinally by water-blocking tapes (uszczelnioną wzdłużnie) | XUHAKXS |
| H | Radial electric field: semiconducting layers (o polu promieniowym) | XUHAKXS |
| A | Aluminium working conductor (z żyłą roboczą aluminiową) | XUHAKXS |
| K | Power cable (kable elektroenergetyczne jednożyłowe) | XUHAKXS |
| XS | Cross-linked polyethylene insulation (izolacji z polietylenu usieciowanego) | XUHAKXS |
| 1 | Normal insulation thickness (o normalnej grubości izolacji) | XUHAKXS |
What the type table says about the names
Quoted from the notes of the type table, with the types they belong to.
- Polish names read outside-in: the sheath letter comes first, then the conductor metal (A = aluminium, none = copper), K, then the insulation. (YKY, YAKY, YKXS, YAKXS, XAKXS, XAKY +13)
- Without the żo mark the cable has NO protective core (3x2,5 = brown, black, grey); with żo the count includes the green-yellow core. (YKY, YAKY, YKXS, YAKXS, XAKXS, XAKY +13)
Every type in PN (Poland)
| Type | Description | Rating |
|---|---|---|
YKY | YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J) | 0,6/1 kV (3,6/6 kV also listed) |
YAKY | YAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J) | 0,6/1 kV |
YKXS | YKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C | 0,6/1 kV |
YAKXS | YAKXS: aluminium power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C (closest VDE: NA2XY-J / NA2XY-O) | 0,6/1 kV |
XAKXS | XAKXS: aluminium power cable, XLPE insulation and PE sheath, 0,6/1 kV, 90 C (closest VDE: NA2X2Y-J / NA2X2Y-O) | 0,6/1 kV |
XAKY | XAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O) | 0,6/1 kV |
YKYY | YKyY: copper power cable with an extruded filler between the cores, PVC insulation and PVC sheath, 0,6/1 kV | 0,6/1 kV |
YAKYY | YAKyY / YAKYy: aluminium power cable with an extruded filler, PVC insulation and PVC sheath, 0,6/1 kV (also listed at 3,6/6 kV) | 0,6/1 kV |
YAKYXS | YAKyXS: aluminium power cable with an extruded filler, XLPE insulation and PVC sheath, 0,6/1 kV | 0,6/1 kV |
YNKY | YnKY: copper power cable like YKY with a self-extinguishing PVC sheath (Yn), 0,6/1 kV | 0,6/1 kV |
YKYFTY | YKYFty: YKY with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV (yn / (n): fire-retardant oversheath, (l): varnished tape) | 0,6/1 kV |
YKYFOY | YKYFoy: YKY with round steel wire armour and a PVC oversheath, 0,6/1 kV ((n): fire-retardant oversheath) | 0,6/1 kV |
YKYEKTMY | YKYektmy: YKY with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV | 0,6/1 kV |
YKXSFTY | YKXSFty: YKXS (XLPE) with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV | 0,6/1 kV |
YKXSEKTMY | YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV | 0,6/1 kV |
YAKYFTY | YAKYFty: YAKY (aluminium, PVC) with galvanised steel tape armour and a PVC oversheath, 0,6/1 kV | 0,6/1 kV |
YAKXSFOY | YAKXSFoy: YAKXS (aluminium, XLPE) with round steel wire armour and a PVC oversheath, 0,6/1 kV | 0,6/1 kV |
YKSYFTY | YKSYFty: control / signalling cable YKSY with steel tape armour and a PVC oversheath, numbered cores, 0,6/1 kV | 0,6/1 kV |
YDY | YDY: round multicore installation wire, solid copper cores, PVC insulation and PVC sheath, 450/750 V | 450/750 V |
YDYP | YDYp: flat installation wire, solid copper cores, PVC insulation and flat PVC sheath, 300/500 V and 450/750 V | 300/500 V and 450/750 V |
YDYT | YDYt: flat installation wire for flush mounting (under plaster), solid copper cores, PVC, 300/500 V (also 450/750 V) | 300/500 V (also 450/750 V) |
YLY | YLY: round multicore wire, stranded copper cores (class 2), PVC insulation and PVC sheath, 0,6/1 kV | 0,6/1 kV |
ADY | ADY: single-core wire with a solid aluminium conductor and PVC insulation, no sheath | not stated by the sources read (UNVERIFIED) |
DY | DY: single-core wire, solid copper conductor, PVC insulation, no sheath (= H05V-U / H07V-U) | 300/500 V and 450/750 V |
LY | LY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R) | 300/500 V and 450/750 V |
LGY | LgY: single-core wire, flexible stranded copper conductor, PVC insulation, no sheath (= H05V-K / H07V-K) | 300/500 V and 450/750 V |
DYC | DYc: single-core wire, solid copper, heat-resistant PVC (90 C) insulation (= H05V2-U / H07V2-U) | 300/500 V and 450/750 V |
LYC | LYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R) | 300/500 V and 450/750 V |
LGYC | LgYc: single-core wire, flexible copper, heat-resistant PVC (90 C) insulation (= H05V2-K / H07V2-K) | 300/500 V and 450/750 V |
OMY | OMY: round household cord, flexible copper, PVC / PVC, 300/300 V (= H03VV-F) | 300/300 V |
OMYP | OMYp: flat household cord, flexible copper, PVC / PVC, 300/300 V (= H03VVH2-F) | 300/300 V |
OWY | OWY: round workshop cord, flexible copper, PVC / PVC, 300/500 V (= H05VV-F) | 300/500 V |
OWYP | OWYp: flat workshop cord, flexible copper, PVC / PVC, 300/500 V (= H05VVH2-F) | 300/500 V |
YKSY | YKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J) | 0,6/1 kV |
YKSLY | YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV | 300/500 V (also 0,6/1 kV) |
YSTY | YStY: control wire (przewod sterowniczy) with PVC insulation and PVC sheath | not stated by the sources read (UNVERIFIED) |
YTDY | YTDY: telecommunication wire, solid copper cores 0,5 mm, PVC insulation and PVC sheath, for alarm and intercom installations | up to 100 V (Eltrim page 124) |
XRUHAKXS | XRUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper screen, radially and longitudinally sealed, PE sheath, 6/10 to 18/30 kV | 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1) |
XRUHKXS | XRUHKXS(1): single-core medium-voltage cable, copper conductor, XLPE insulation, copper screen, radially and longitudinally sealed, PE sheath, 6/10 to 18/30 kV | 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1) |
XnRUHAKXS | XnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV | 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1) |
XUHAKXS | XUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen sealed longitudinally (water-blocking tapes), PE sheath, 6/10 to 18/30 kV (= NA2XS(F)2Y) | 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1) |
XnUHAKXS | XnUHAKXS(1): XUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen sealed longitudinally, 6/10 to 18/30 kV | 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1) |
Marks written next to the name
Words and marks the decoder reads next to a type name of this system: each adds a property to whatever type it is written with.
| Mark | Meaning | Written as |
|---|---|---|
| żo | Includes a green-yellow protective core ("zyla ochronna"); without the mark the cable has no protective core. Typed ZO without the accent, or in parentheses, it means the same | ŻO ZO |
| RE | Conductor shape: round, solid, class 1 | RE |
| RM | Conductor shape: round, stranded, class 2 | RM |
| RMC | Conductor shape: round, stranded, compacted, class 2 | RMC |
| SM | Conductor shape: sector, stranded, class 2 | SM |
| SE | Conductor shape: sector, solid, class 1 (read by analogy; SE itself is not defined on a page read, UNVERIFIED) | SE |
| ekw | Common screen on the core | EKW |
| ekwf | Common foil screen on the core | EKWF |
| eko | Screen of round wires (braid) | EKO |
| ekp | Individually screened pairs | EKP |
| ekt | Tape screen | EKT |
Common questions
What is LYC cable?
LYC: LYc: single-core wire, stranded copper, heat-resistant PVC (90 C) insulation (= H05V2-R / H07V2-R). Rating: 300/500 V and 450/750 V. Standard: harmonised type (the PN standard number is not named by the sources read). The name reads: L (Stranded copper conductor, class 2) + Yc (Heat-resistant PVC (90 C) insulation).
What is LY cable?
LY: single-core wire, stranded copper conductor (class 2), PVC insulation, no sheath (= H05V-R / H07V-R). Rating: 300/500 V and 450/750 V. Standard: harmonised type (the PN standard number is not named by the sources read). The name reads: L (Stranded (multi-wire) copper conductor, class 2) + Y (PVC insulation).
What is the difference between YKY and YAKY?
YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J), 0,6/1 kV (3,6/6 kV also listed). YAKY: aluminium power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NAYY-O / NAYY-J), 0,6/1 kV. The names differ in: YAKY: A (Aluminium conductor (no letter: copper)).
PN (Poland): what does Y mean in a cable name?
Y has more than one meaning, depending on the type: PVC insulation (YKY, YAKY, XAKY, YKYY +19); PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names (YKYFTY, YKYFOY, YKYEKTMY, YKXSFTY +4); PVC sheath; the sheath letter comes first in Polish names (YKY, YAKY, YKXS, YAKXS +3); PVC sheath (YDY, YDYP, YDYT, YLY +3); PVC (insulation and sheath) (OMY, OMYP, OWY, OWYP); PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing) (YKSLY).
PN (Poland): what does żo mean next to a cable name?
żo: Includes a green-yellow protective core ("zyla ochronna"); without the mark the cable has no protective core. Typed ZO without the accent, or in parentheses, it means the same. Written as ŻO, ZO.
What is YKY cable?
YKY: copper power cable, PVC insulation and PVC sheath, 0,6/1 kV (closest VDE: NYY-O, with żo NYY-J). Rating: 0,6/1 kV (3,6/6 kV also listed). Standard: PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue). The name reads: Y (PVC sheath; the sheath letter comes first in Polish names) + K (kabel: power cable family (not a copper letter)) + Y (PVC insulation).
Sources the type table names
Standards named in the table
- PN-93/E-90400
- PN-93/E-90401
- PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue)
- PN-HD 603 S1:2006/A3:2009
- IEC 60502-1
- PN-EN 50525-1
- NF-EP-66:2012 (as printed in the Elpar catalogue)
- NF-EP-12:2008 (as printed in the Elpar catalogue)
- not stated by the sources read (letter key only)
- harmonised type (the PN standard number is not named by the sources read)
- PN-HD 21.5 S3:2004
- PN-91/E-90103 (as printed by Eltrim)
- PN-HD 21.5 S3:2004 family (as printed by Eltrim)
- PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim)
- Elpar ARCONTROL range (standard number not named by the pages read)
- not stated by the sources read (listed in the Elpar key and product list)
- ZN-ELT-2/2007 (Eltrim in-house)
- HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27)
- XLPE DIX 8 (1, p. 10-R-3). seen: standard
- PN-HD 620 S3:2023-04 (makers)
- HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Tables 8 and 10 (pp. 10-R-29, 10-R-30)
- HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 7 (p. 10-R-28)
- PN-HD 620-10C (older maker sheet)
Documents and pages the readings were taken from
- mail.elpar.pl/uploads/download/katalog_kable_i_przewody_elektroenergety…
- media.solar.pl/mdm/data/technicals/318E2A9818DE2099F73D204370D7A48C.pdf
- praktycznie-elektryka.blogspot.com/2017/09/teoria-o-kablach-i-przewodac…
- energetyka.plus/kable-energetyczne-nn-stosowane-w-polsce
- nowaelektro.pl/yakxs
- elpar.pl/produkty/getPdf/id/31
- muratordom.pl/instalacje/instalacja-elektryczna/oznaczenia-przewodow-el…
- el12.com/en/cables-and-wires/lgy-1x6-cable-h07v-k-green-5907702814087,i…
- castorama.pl/kabel-instalacyjny-omyp-2-x-0-75-mm-5-m-bialy/590160219511…
- HD 620 S3:2023 10-R Table 5, p. 10-R-26; Tables 6 to 8, pp. 10-R-27 to 10-R-29; No. 7, 9, p. 10-R-7
- tele-fonika.com/storage/file/core_files/2025/9/1/962c7cb46962c67bd5ddb3…
- elpar.pl/produkt/xruhakxs-6-10kv-8-7-15kv-12-20kv-18-30kv
- elpar.elpar.pl/produkty/getPdf/id/386
- sklep.fega.pl/amfile/file/download/file/764342/product/8780
Taken from the type table of this site, with the sources named above. Check the manufacturer's datasheet before you specify a cable.