XUHAKXS
XUHAKXS is a PN (Poland) cable designation: X = Thermoplastic polyethylene sheath (powłoka z polietylenu termoplastycznego); U = Return conductor sealed longitudinally by water-blocking tapes (uszczelnioną wzdłużnie); H = Radial electric field: semiconducting layers (o polu promieniowym); A = Aluminium working conductor (z żyłą roboczą aluminiową); K = Power cable (kable elektroenergetyczne jednożyłowe); XS = Cross-linked polyethylene insulation (izolacji z polietylenu usieciowanego); 1 = Normal insulation thickness (o normalnej grubości izolacji); XUHAKXS = XUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen sealed longitudinally (water-blocking tapes), PE sheath, 6/10 to 18/30 kV (= NA2XS(F)2Y). 6/10, 8,7/15, 12/20 and 18/30 kV. PN-HD 620 S3:2023-04, parts 0, 1 and 10R (Elpar); PN-HD 620-10C (older maker sheet).
1 coding system recognises this code
PN (Poland)
| Symbol | Meaning |
|---|---|
X | Thermoplastic polyethylene sheath (powłoka z polietylenu termoplastycznego) |
U | Return conductor sealed longitudinally by water-blocking tapes (uszczelnioną wzdłużnie) |
H | Radial electric field: semiconducting layers (o polu promieniowym) |
A | Aluminium working conductor (z żyłą roboczą aluminiową) |
K | Power cable (kable elektroenergetyczne jednożyłowe) |
XS | Cross-linked polyethylene insulation (izolacji z polietylenu usieciowanego) |
1 | Normal insulation thickness (o normalnej grubości izolacji) |
XUHAKXS | XUHAKXS(1): single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen sealed longitudinally (water-blocking tapes), PE sheath, 6/10 to 18/30 kV (= NA2XS(F)2Y). 6/10, 8,7/15, 12/20 and 18/30 kV. PN-HD 620 S3:2023-04, parts 0, 1 and 10R (Elpar); PN-HD 620-10C (older maker sheet) |
Fire behaviour (EU CPR)
PE sheath (X).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.