XnRUHAKXS

XnRUHAKXS is a PN (Poland) cable designation: Xn = Xn: flame retardant PE sheath (HD 620 S3 10-R Table 5); R = R: transversal (radial) water tightness, a metal foil bonded to the PE sheath (HD 620 S3 10-R Table 5, No. 9); U = Longitudinally sealed: water-blocking tapes; H = H: radial field (HD 620 S3 10-R Table 5); A = Aluminium working conductor; K = kabel: power cable family; XS = Cross-linked polyethylene (XLPE) insulation; 1 = Type 1: normal insulation thickness; XnRUHAKXS = XnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV. 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1). HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27); XLPE DIX 8 (1, p. 10-R-3). seen: standard; PN-HD 620 S3:2023-04 (makers).

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of XnRUHAKXS:

  • XnRUHAKXS: Xn = Xn: flame retardant PE sheath (HD 620 S3 10-R Table 5); R = R: transversal (radial) water tightness, a metal foil bonded to the PE sheath (HD 620 S3 10-R Table 5, No. 9); U = Longitudinally sealed: water-blocking tapes; H = H: radial field (HD 620 S3 10-R Table 5); A = Aluminium working conductor; K = kabel: power cable family; XS = Cross-linked polyethylene (XLPE) insulation; 1 = Type 1: normal insulation thickness; XnRUHAKXS = XnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV. 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1). HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27); XLPE DIX 8 (1, p. 10-R-3). seen: standard; PN-HD 620 S3:2023-04 (makers)

Related cable types: XRUHAKXS · XnUHAKXS · XRUHKXS · XUHAKXS

PN (Poland)

SymbolMeaning
XnXn: flame retardant PE sheath (HD 620 S3 10-R Table 5)
RR: transversal (radial) water tightness, a metal foil bonded to the PE sheath (HD 620 S3 10-R Table 5, No. 9)
ULongitudinally sealed: water-blocking tapes
HH: radial field (HD 620 S3 10-R Table 5)
AAluminium working conductor
Kkabel: power cable family
XSCross-linked polyethylene (XLPE) insulation
1Type 1: normal insulation thickness
XnRUHAKXSXnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV. 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1). HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27); XLPE DIX 8 (1, p. 10-R-3). seen: standard; PN-HD 620 S3:2023-04 (makers)

What is XnRUHAKXS cable?

XnRUHAKXS: XnRUHAKXS(1): XRUHAKXS with a flame retardant PE sheath: single-core medium-voltage cable, aluminium conductor, XLPE, copper screen, radially and longitudinally sealed, 6/10 to 18/30 kV. Rating: 6/10, 8,7/15, 12/20 and 18/30 kV; 90 C conductor, 250 C short circuit (5 s) (HD 620 S3 10-R 1). Standard: HD 620 S3:2023 section 10-R, Table 5 type designations (p. 10-R-26) and Table 6 (p. 10-R-27); XLPE DIX 8 (1, p. 10-R-3). seen: standard; PN-HD 620 S3:2023-04 (makers).

Table 6 of HD 620 S3 10-R gives XnRUHAKXS and XRUHAKXS the same dimensions; Xn is the flame retardant PE sheath (Table 5).

Documents and pages the readings were taken from

  • HD 620 S3:2023 10-R Table 5, p. 10-R-26; Tables 6 to 8, pp. 10-R-27 to 10-R-29; No. 7, 9, p. 10-R-7

PN (Poland): how to read the cable type names

Fire behaviour (EU CPR)

  • Flame retardant (Xn, XnRUHAKXS). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PE sheath (Xn).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Work with XnRUHAKXS

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More PN (Poland) designations

XnRUHAKXS