XAKY

XAKY is a PN (Poland) cable designation: X = polyethylene (PE) sheath; the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); Y = PVC insulation; XAKY = XAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O). 0,6/1 kV. PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of XAKY 1x16 0.6/1 kV:

  • XAKY: X = polyethylene (PE) sheath; the sheath letter comes first in Polish names; A = Aluminium conductor (no letter: copper); K = kabel: power cable family (not a copper letter); Y = PVC insulation; XAKY = XAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O). 0,6/1 kV. PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue)
  • 1x16 0.6/1 kV: one core, aluminium 16 mm²; rated voltage 0.6/1 kV

Related cable types: YAKY

PN (Poland)

SymbolMeaning
Xpolyethylene (PE) sheath; the sheath letter comes first in Polish names
AAluminium conductor (no letter: copper)
Kkabel: power cable family (not a copper letter)
YPVC insulation
XAKYXAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O). 0,6/1 kV. PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue)

What is XAKY cable?

XAKY: aluminium power cable, PVC insulation and PE sheath, 0,6/1 kV (closest VDE: NAY2Y-J / NAY2Y-O). Rating: 0,6/1 kV. Standard: PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue).

Polish names read outside-in: the sheath letter comes first, then the conductor metal (A = aluminium, none = copper), K, then the insulation. Without the żo mark the cable has NO protective core (3x2,5 = brown, black, grey); with żo the count includes the green-yellow core. Closest VDE type NAY2Y-J / NAY2Y-O (energetyka.plus). No product page of this type was read; the reading follows the letter key (X = PE sheath, A, K, Y = PVC insulation).

Documents and pages the readings were taken from

PN (Poland): how to read the cable type names

Fire behaviour (EU CPR)

  • PVC sheath (XAKY).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

  • PE sheath (X).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

XAKY: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NAY2Y 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules
IndiaIS 1554 (Part 1)AYY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath material PE → PVC; Sheath 1.4 → 1.8 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

XAKY as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 110 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
SheathPE1.49.7

XAKY on a drum

The smallest drum that passes every check, for 9.7 mm and about 110 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1462 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16141–145 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: XAKY

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 59 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.4 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

XAKY belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with XAKY

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More PN (Poland) designations

XAKY