YKXS
YKXS is a PN (Poland) cable designation: Y = PVC sheath; the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; YKXS = YKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of YKXS 1x16 0.6/1 kV:
YKXS: Y = PVC sheath; the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; YKXS = YKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-11x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV
PN (Poland)
| Symbol | Meaning |
|---|---|
Y | PVC sheath; the sheath letter comes first in Polish names |
K | kabel: power cable family (not a copper letter) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
YKXS | YKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
What is YKXS cable?
YKXS: copper power cable, XLPE insulation and PVC sheath, 0,6/1 kV, 90 C. Rating: 0,6/1 kV. Standard: PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
Polish names read outside-in: the sheath letter comes first, then the conductor metal (A = aluminium, none = copper), K, then the insulation. Without the żo mark the cable has NO protective core (3x2,5 = brown, black, grey); with żo the count includes the green-yellow core. No VDE equivalent is stated on the pages read (N2XY is not confirmed).
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (Y, YKXS).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
YKXS: equivalents in other countries
Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | N2XY 1x16 RM 0,6/1 kV | Close | Sheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm |
| India | IS 7098 (Part 1) | 2XY 1x16 1100 V | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm; this cable as built misses 1 of its rules |
| South Africa | SANS 1507-4 | no letters for this build | Close | Inner covering / bedding material: only in the equivalent; Wire armour material: only in the equivalent; Overall diameter 9.1 → 12.5 mm |
No equivalent in: BS 5467 (not in its cable tables, armoured cables only); BS 6724 (not in its cable tables, armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
YKXS as the cable designer builds it, 1x16 0.6/1 kV
Overall diameter 9.1 mm, about 210 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 6.3 |
| Sheath | PVC | 1.4 | 9.1 |
YKXS on a drum
The smallest drum that passes every check, for 9.1 mm and about 210 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 14 | 112 kg |
| 1,000 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 15 of 17 | 241–245 kg |
Barrel at least 20 × OD = 182 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: YKXS
YKXS belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables