YKSLY
YKSLY is a PN (Poland) cable designation: Y = PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing); KS = Signalling / control cable family (K cable, S signalling); L = Stranded copper conductor; Y = PVC insulation; YKSLY = YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. 300/500 V (also 0,6/1 kV). Elpar ARCONTROL range (standard number not named by the pages read).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of YKSLY 1x16 0.6/1 kV:
YKSLY: Y = PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing); KS = Signalling / control cable family (K cable, S signalling); L = Stranded copper conductor; Y = PVC insulation; YKSLY = YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. 300/500 V (also 0,6/1 kV). Elpar ARCONTROL range (standard number not named by the pages read)1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV
PN (Poland)
| Symbol | Meaning |
|---|---|
Y | PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing) |
KS | Signalling / control cable family (K cable, S signalling) |
L | Stranded copper conductor |
Y | PVC insulation |
YKSLY | YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. 300/500 V (also 0,6/1 kV). Elpar ARCONTROL range (standard number not named by the pages read) |
What is YKSLY cable?
YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. Rating: 300/500 V (also 0,6/1 kV). Standard: Elpar ARCONTROL range (standard number not named by the pages read).
The Elpar template example reads "Y KS L Y ekw żo": a common screen (ekw) is a variant. The printed name "Y(Yc, Yo, Yn)KSLY(żo)" is a family heading, not a spelling to type. Numbered cores.
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
YKSLY: equivalents in other countries
Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 3-G (DIN VDE 0276-603) | NYY 1x16 RM 0,6/1 kV | Close | Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules |
| India | IS 1554 (Part 1) | YY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
YKSLY as the cable designer builds it, 1x16 0.6/1 kV
Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Sheath | PVC | 1.4 | 9.7 |
YKSLY on a drum
The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 14 | 117 kg |
| 1,000 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 16 of 16 | 251–255 kg |
Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: YKSLY
YKSLY belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with YKSLY
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.