YKSY

YKSY is a PN (Poland) cable designation: Y = PVC sheath; KS = Signalling / control cable family (K cable, S signalling); Y = PVC insulation; YKSY = YKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J). 0,6/1 kV. PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of YKSY 4x1.5 0.6/1 kV:

  • YKSY: Y = PVC sheath; KS = Signalling / control cable family (K cable, S signalling); Y = PVC insulation; YKSY = YKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J). 0,6/1 kV. PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim)
  • 4x1.5 0.6/1 kV: 4 cores, each copper 1.5 mm²; rated voltage 0.6/1 kV

Related cable types: YKSYFTY · YKY · YKYY · YKSLY

PN (Poland)

SymbolMeaning
YPVC sheath
KSSignalling / control cable family (K cable, S signalling)
YPVC insulation
YKSYYKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J). 0,6/1 kV. PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim)

What is YKSY cable?

YKSY: control / signalling cable, solid copper cores, numbered, PVC / PVC, 0,6/1 kV, 7 to 75 cores (closest VDE: NYY-J). Rating: 0,6/1 kV. Standard: PN-93/E-90403 (+ PN-HD 516 S2:2003) (as printed by Eltrim).

Eltrim page 26 states the equivalent NYY-J. Numbered black cores plus a green-yellow one with żo. Polish names read outside-in: the sheath letter comes first, then the conductor metal (A = aluminium, none = copper), K, then the insulation. Without the żo mark the cable has NO protective core (3x2,5 = brown, black, grey); with żo the count includes the green-yellow core.

Documents and pages the readings were taken from

PN (Poland): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

YKSY: equivalents in other countries

Shown for 4x1.5 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYY 4x1,5 RE 0,6/1 kVEquivalentevery value the same
IndiaIS 1554 (Part 1)YY 4x1,5 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 12.8 → 11.4 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

YKSY as the cable designer builds it, 4x1.5 0.6/1 kV

Overall diameter 12.8 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.803.0
FillerPP7.2
Inner covering / beddingPVC1.09.2
SheathPVC1.812.8

YKSY on a drum

The smallest drum that passes every check, for 12.8 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG11 of 12141–145 kg
1,000 mKTG 9 (900 mm flange), wood KTG drums (Europe), Bayka, KTG13 of 14267–271 kg

Barrel at least 15 × OD = 192 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: YKSY

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 18 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 10.2 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 3, p. 12; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

YKSY belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables