NA2XS(FL)2Y 1x120 RM/16 12/20 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, NA2XS(FL)2Y 1x120 RM/16 12/20 kV comes to an overall diameter of about 34.3 mm and a weight of about 1,170 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

Main dimensions

ConductorAluminium 120 mm² RM, Ø 12.9 mmIEC 60228 class 2 compacted, middle of min / max
InsulationXLPE 5.5 mmIEC 60502-2:2014 Tables 5-7, nominal insulation thickness
Diameter over insulation25.1 mm
Overall diameter34.3 mm
Weight (approximate)1,170 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1Conductor screen (semicon)Semiconducting0.614.1TKF at least 0.5 mm, Nexans under 1 mmtypical value, no rule
2InsulationXLPE5.525.1IEC 60502-2:2014 Tables 5-7, nominal insulation thicknessread in the standard
3Insulation screen (semicon)Semiconducting0.826.7TKF 0.8 mm, Nexans about 1 mmtypical value, no rule
4Swelling tape (water block)Swelling0.427.5typical swelling tapetypical value, no rule
5Wire screenCopper42 wires of 0.70 mm, 16 mm²29.1copper wire screen: wires at least 0.5 mm, 0.1 mm counter-helix tapetypical value, no rule
6Swelling tape (water block)Swelling0.429.9typical swelling tapetypical value, no rule
7Laminate (radial water block)Aluminium0.230.3typical aluminium laminate bonded to the sheathtypical value, no rule
8SheathPE2.034.3IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Sources and page numbers: research/mv-dimensions in the site repository.

Weight, by part

Conductors330 kg/km
Metal screens and armour200 kg/km
Insulation, semicon, tapes, fillers and sheaths650 kg/km
Total1,170 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).