NA2XS(F)Y dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of NA2XS(F)Y, sized by the IEC rules the designer uses. Open a row for every layer and its source. What NA2XS(F)Y means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.528.8850
1x7012/20 kV5.530.6970
1x9512/20 kV5.532.31,090
1x12012/20 kV5.533.91,220
1x15012/20 kV5.535.41,430
1x18512/20 kV5.537.31,600
1x24012/20 kV5.539.61,830
1x30012/20 kV5.542.02,080
1x40012/20 kV5.545.12,560
1x50012/20 kV5.548.22,960
1x956/10 kV3.427.9900
1x1506/10 kV3.431.01,210
1x2406/10 kV3.435.21,580
1x3006/10 kV3.437.71,820
1x4006/10 kV3.440.62,270
1x9518/30 kV8.037.71,380
1x15018/30 kV8.040.71,750
1x24018/30 kV8.045.02,180
1x30018/30 kV8.047.42,450
1x40018/30 kV8.050.42,950