N2XS2Y dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of N2XS2Y, sized by the IEC rules the designer uses. Open a row for every layer and its source. What N2XS2Y means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.527.21,050
1x7012/20 kV5.529.01,280
1x9512/20 kV5.530.71,550
1x12012/20 kV5.532.31,830
1x15012/20 kV5.533.82,220
1x18512/20 kV5.535.72,590
1x24012/20 kV5.538.03,150
1x30012/20 kV5.540.43,770
1x40012/20 kV5.543.54,860
1x50012/20 kV5.546.75,860
1x956/10 kV3.426.31,380
1x1506/10 kV3.429.42,020
1x2406/10 kV3.433.62,930
1x3006/10 kV3.436.13,530
1x4006/10 kV3.439.14,600
1x9518/30 kV8.036.11,800
1x15018/30 kV8.039.22,490
1x24018/30 kV8.043.43,460
1x30018/30 kV8.045.84,100
1x40018/30 kV8.048.95,210

Cable dimensions