NA2XSY dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of NA2XSY, sized by the IEC rules the designer uses. Open a row for every layer and its source. What NA2XSY means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.527.2800
1x7012/20 kV5.529.0920
1x9512/20 kV5.530.71,040
1x12012/20 kV5.532.31,160
1x15012/20 kV5.533.81,370
1x18512/20 kV5.535.71,540
1x24012/20 kV5.538.01,760
1x30012/20 kV5.540.42,010
1x40012/20 kV5.543.52,480
1x50012/20 kV5.546.72,870
1x956/10 kV3.426.3850
1x1506/10 kV3.429.41,160
1x2406/10 kV3.433.61,520
1x3006/10 kV3.436.11,750
1x4006/10 kV3.439.12,210
1x9518/30 kV8.036.11,320
1x15018/30 kV8.039.21,680
1x24018/30 kV8.043.42,100
1x30018/30 kV8.045.82,370
1x40018/30 kV8.048.92,870

Cable dimensions