N2XS(FL)2Y dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of N2XS(FL)2Y, sized by the IEC rules the designer uses. Open a row for every layer and its source. What N2XS(FL)2Y means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.528.81,120
1x7012/20 kV5.530.61,360
1x9512/20 kV5.532.31,640
1x12012/20 kV5.533.91,920
1x15012/20 kV5.535.42,310
1x18512/20 kV5.537.32,690
1x24012/20 kV5.539.63,260
1x30012/20 kV5.542.13,880
1x40012/20 kV5.545.14,980
1x50012/20 kV5.548.35,990
1x956/10 kV3.427.91,450
1x1506/10 kV3.431.02,110
1x2406/10 kV3.435.23,030
1x3006/10 kV3.437.73,640
1x4006/10 kV3.440.74,710
1x9518/30 kV8.037.71,910
1x15018/30 kV8.040.82,600
1x24018/30 kV8.045.03,590
1x30018/30 kV8.047.44,230
1x40018/30 kV8.050.55,350

Who makes or stocks this cable?

Cable dimensions