N2XS(FL)2Y 1x120 RM/16 12/20 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, N2XS(FL)2Y 1x120 RM/16 12/20 kV comes to an overall diameter of about 33.9 mm and a weight of about 1,920 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorCopper 120 mm² RM, Ø 12.9 mmIEC 60228 class 2 compacted, middle of min / max
InsulationXLPE 5.5 mmIEC 60502-2:2014 Tables 5-7, nominal insulation thickness
Diameter over insulation25.1 mm
Overall diameter33.9 mm
Weight (approximate)1,920 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1Conductor screen (semicon)Semiconducting0.614.1TKF at least 0.5 mm, Nexans under 1 mmtypical value, no rule
2InsulationXLPE5.525.1IEC 60502-2:2014 Tables 5-7, nominal insulation thicknessread in the standard
3Insulation screen (semicon)Semiconducting0.826.7TKF 0.8 mm, Nexans about 1 mmtypical value, no rule
4Swelling tape (water block)Swelling0.327.3typical swelling tape 0.30 mm; a wound tape at most 70 mm widetypical value, no rule
5Wire screenCopper42 wires of 0.70 mm, 16 mm²28.9copper wire screen: wires at least 0.5 mm (0.7 mm, thicker when the section does not fit), 0.1 mm counter-helix tapetypical value, no rule
6Swelling tape (water block)Swelling0.329.5typical swelling tape 0.30 mm; a wound tape at most 70 mm widetypical value, no rule
7Laminate (radial water block)Aluminium0.229.9typical aluminium laminate bonded to the sheathtypical value, no rule
8SheathPE2.033.9IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Sources and page numbers: research/mv-dimensions in the site repository.

Materials in this cable: Copper, Aluminium, XLPE, PE, Semiconductive compound

Weight, by part

Conductors1,090 kg/km
Metal screens and armour200 kg/km
Insulation, semicon, tapes, fillers and sheaths630 kg/km
Total1,920 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

N2XS(FL)2Y 1x120 RM/16 12/20 kV: equivalents in other countries

Shown for 1x120/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
NetherlandsHD 620 S3 10-JYMeKrvasdlwd 12/20 kV 1x120 rs +as16 (key read from a maker (Nedkab), the NEN text not seen)EquivalentInsulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 34.5 → 34.9 mm
DenmarkHD 620 S3 10-Dno letters for this buildCloseInsulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2 mm; Overall diameter 34.5 → 33.9 mm
International (IEC)IEC 60502Cu/XLPE/CWS/PE 1x120/16 12/20 kV (to IEC 60502-2)CloseInsulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2 mm; Overall diameter 34.5 → 33.9 mm
SwedenHD 620 S3 10-MFXCLJ-TT 1x120/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ))Closescreen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Sheath 2.5 → 2 mm; Overall diameter 34.5 → 33.5 mm; this cable as built misses 1 of its rules
NorwayHD 620 S3 10-KTSLF 24 kV 1 x 120 mm2 (provisional code designation of HD 620 10-K Table 4; F is a PE sheath with an outer conducting layer, which this build does not draw)Closescreen 16 → 25 mm² (HD 620 10-K Table 1); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2 mm; Overall diameter 34.5 → 33.9 mm; this cable as built misses 1 of its rules

No equivalent in: BS 6622 (armoured cables only).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.