N2XSY dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of N2XSY, sized by the IEC rules the designer uses. Open a row for every layer and its source. What N2XSY means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.527.21,120
1x7012/20 kV5.529.01,360
1x9512/20 kV5.530.71,640
1x12012/20 kV5.532.31,920
1x15012/20 kV5.533.82,320
1x18512/20 kV5.535.72,700
1x24012/20 kV5.538.03,270
1x30012/20 kV5.540.43,900
1x40012/20 kV5.543.55,010
1x50012/20 kV5.546.76,030
1x956/10 kV3.426.31,450
1x1506/10 kV3.429.42,110
1x2406/10 kV3.433.63,030
1x3006/10 kV3.436.13,650
1x4006/10 kV3.439.14,730
1x9518/30 kV8.036.11,920
1x15018/30 kV8.039.22,620
1x24018/30 kV8.043.43,610
1x30018/30 kV8.045.84,270
1x40018/30 kV8.048.95,390

Cable dimensions