NA2XS(F)2Y dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of NA2XS(F)2Y, sized by the IEC rules the designer uses. Open a row for every layer and its source. What NA2XS(F)2Y means, letter by letter.

Medium voltage, single core · 20 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x5012/20 kV5.528.8780
1x7012/20 kV5.530.6880
1x9512/20 kV5.532.31,000
1x12012/20 kV5.533.91,120
1x15012/20 kV5.535.41,330
1x18512/20 kV5.537.31,480
1x24012/20 kV5.539.61,700
1x30012/20 kV5.542.01,940
1x40012/20 kV5.545.12,400
1x50012/20 kV5.548.22,780
1x956/10 kV3.427.9820
1x1506/10 kV3.431.01,120
1x2406/10 kV3.435.21,470
1x3006/10 kV3.437.71,700
1x4006/10 kV3.440.62,140
1x9518/30 kV8.037.71,260
1x15018/30 kV8.040.71,610
1x24018/30 kV8.045.02,020
1x30018/30 kV8.047.42,280
1x40018/30 kV8.050.42,760

Cable dimensions