N2XS(F)2Y 1x95 RM/16 6/10 kV
IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.
By the IEC construction rules, N2XS(F)2Y 1x95 RM/16 6/10 kV comes to an overall diameter of about 27.9 mm and a weight of about 1,420 kg/km.
Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.
Main dimensions
| Conductor | Copper 95 mm² RM, Ø 11.5 mm | IEC 60228 class 2 compacted, middle of min / max |
|---|---|---|
| Insulation | XLPE 3.4 mm | IEC 60502-2:2014 Tables 5-7, nominal insulation thickness |
| Diameter over insulation | 19.5 mm | |
| Overall diameter | 27.9 mm | |
| Weight (approximate) | 1,420 kg/km |
Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).
Layer by layer (inside out)
| # | Layer | Material | Thickness mm | Ø over mm | Source | How firmly |
|---|---|---|---|---|---|---|
| 1 | Conductor screen (semicon) | Semiconducting | 0.6 | 12.7 | TKF at least 0.5 mm, Nexans under 1 mm | typical value, no rule |
| 2 | Insulation | XLPE | 3.4 | 19.5 | IEC 60502-2:2014 Tables 5-7, nominal insulation thickness | read in the standard |
| 3 | Insulation screen (semicon) | Semiconducting | 0.8 | 21.1 | TKF 0.8 mm, Nexans about 1 mm | typical value, no rule |
| 4 | Swelling tape (water block) | Swelling | 0.4 | 21.9 | typical swelling tape | typical value, no rule |
| 5 | Wire screen | Copper | 42 wires of 0.70 mm, 16 mm² | 23.5 | copper wire screen: wires at least 0.5 mm, 0.1 mm counter-helix tape | typical value, no rule |
| 6 | Swelling tape (water block) | Swelling | 0.4 | 24.3 | typical swelling tape | typical value, no rule |
| 7 | Sheath | PE | 1.8 | 27.9 | IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A) | read in the standard |
Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Sources and page numbers: research/mv-dimensions in the site repository.
Weight, by part
| Conductors | 860 kg/km |
| Metal screens and armour | 150 kg/km |
| Insulation, semicon, tapes, fillers and sheaths | 410 kg/km |
| Total | 1,420 kg/km |
|---|
Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).