XHHW-2

XHHW-2 is a NEC / UL (USA) cable designation: X = Thermoset (cross-linked polyethylene) insulation; HH = High heat resistant, 90 C; W = Approved for wet locations; -2 = 90 C in both wet and dry locations; XHHW-2 = Thermoset (XLPE) high heat-resistant building wire, 90 C wet or dry. 600 V, 90 C wet and dry. UL 44; NEC Article 310.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: UL 44 (edition 19): Thermoset-Insulated Wires and Cables. How the values are sourced

Worked reading of XHHW-2 12 AWG, 600 V:

  • XHHW-2: X = Thermoset (cross-linked polyethylene) insulation; HH = High heat resistant, 90 C; W = Approved for wet locations; -2 = 90 C in both wet and dry locations; XHHW-2 = Thermoset (XLPE) high heat-resistant building wire, 90 C wet or dry. 600 V, 90 C wet and dry. UL 44; NEC Article 310
  • 12 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V

Related cable types: XHHW-2-LS · TC (XHHW-2)

NEC / UL (USA)

SymbolMeaning
XThermoset (cross-linked polyethylene) insulation
HHHigh heat resistant, 90 C
WApproved for wet locations
-290 C in both wet and dry locations
XHHW-2Thermoset (XLPE) high heat-resistant building wire, 90 C wet or dry. 600 V, 90 C wet and dry. UL 44; NEC Article 310

NEC Article 310 (US building wire, NFPA 70)

SymbolMeaning
XCross-Linked Polymer Insulation
HH90°C Insulation
WMoisture Resistant
-2With Insulation For Use In Wet Or Dry Locations At Max. Temp. 90°C

How to read a NEC Article 310 (US building wire, NFPA 70) cable code

What is XHHW-2 cable?

XHHW-2: Thermoset (XLPE) high heat-resistant building wire, 90 C wet or dry. Rating: 600 V, 90 C wet and dry. Standard: UL 44; NEC Article 310.

No outer covering. Copper or aluminium; an "AL" in the text switches the metal. Often dual-marked RW90 in Canada.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

XHHW-2 dimensions and weight

Every XHHW-2 size

XHHW-2: equivalents in other countries

Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502no letters for this buildCloseInsulation 0.76 → 0.7 mm; Overall diameter 3.79 → 3.67 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

XHHW-2 as the cable designer builds it, 12 AWG, 600 V

Overall diameter 3.8 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.763.8

XHHW-2 on a drum

The smallest drum that passes every check, for 3.8 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 14x10x5, wood NEMA reels (North America), Okonite15 of 1822 kg
1,000 mNEMA 18x10x6, wood NEMA reels (North America), Okonite23 of 2945 kg

Barrel at least 20 × OD = 76 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: XHHW-2

XHHW-2 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²